APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN TABLE/
SUB-TABLE

CCN POINT

PAGE NO.

COOL (cont)

Cooling Configuration

COOL_CFG

15

3.ON

Fan Lev3 On Temperature

0 to 100

°F

no Humidi­MiZer FIOP:
65
Humidi­MiZer FIOP:
88 (20, PM16)
68 (24­28)(PG03­16)

LEV3ON

3.OFF

Fan Lev3 Off Temperature

0 to 100

°F

no Humidi­MiZer FIOP:
55
Humidi­MiZer FIOP:
78 (20, PM16)
62 (24­28)(PG03­16)

LEV3OFF

HMZR

Humidimizer Config

HMZR_CFG

24

REHT

Humidimizer Equipped

No/Yes

No: no Humidi­MiZer
FIOP
Yes: Humidi­MiZer FIOP

REHEAT

24

R.DEC

Reheat2 Stage Decr.
Time

0 to 999

secs

60

RSTAGDEC

28

R.INC

Reheat2 Stage Incr. Time

0 to 999

secs

300

RSTAGINC

28

RH.FN

Reheat Fan Control

No/Yes

No (03­14)
Yes (16­28)

RHFANCTL

28

RF.LV

Reheat ODF Fan On
Level

0 to 3

2 (03­20)
3 (24­28)

RHFANLEV

28

RF. ON

Reheat ODF Fan On
Temp

0 to 100

°F

75 (PG03­16)
93 (PG20­24)(PM16­28)
85 (PG 28)

RHFANON

28

RF.OF

Reheat ODF Fan Off
Temp

0 to 100

°F

70 (PG03­16)
83 (20, PM16)
88 (24)(PM 28)
80 (PG 28)

RHFANOFF

28

RA.LO

Reheat2 OAT Limit A

20 to 70

°F

40

OATLRH_A

28

RA.LP

Reheat2 SSP Lo Limit A

50 to 100

psig

80

RHSSPL_A

28

RA.HP

Reheat2 SSP Hi Limit A

50 to 100

psig

90

RHSSPH_A

28

RB.LO

Reheat2 OAT Limit B,C

20 to 70

°F

50

OATLRH_B

28

RB.LP

Reheat2 SSP Lo Limit
B,C

50 to 100

psig

80

RHSSPL_B

28

RB.HP

Reheat2 SSP Hi Limit B,C

50 to 100

psig

90

RHSSPH_B

28

HEAT

Heating Configuration

HEAT_CFG

15

HT.TY

Type of Heat Installed

0=No Heat
1=Gas
2=Electric

0 (50 series with no elec­
tric heat)
1 (48 series)
2 (50 series with electric
heat)

HEATTYPE

21

N.HTR

Number of Heat Stages

1 to 2

1 (48 series 1­phase, 50
series <15kW)
2 (48 series 3­phase, 50
series >=15kW)

NUM_HEAT

22

MRT.H

Heat Minimum On Time

60 to 999

sec

120

HMIN_ON

22

MOT.H

Heat Minimum Off Time

60 to 999

sec

120

HMIN_OFF

22

H.DEC

Heat Stage Decrease
Time

120 to 999

sec

300

HSTAGDEC

21

H.INC

Heat Stage Increase
Time

120 to 999

sec

450

HSTAGINC

21

FOD.E

Fan­off Delay, Elect Heat

10 to 600

sec

30

ELEC_FOD

17

FOD.G

Fan­off Delay, Gas Heat

45 to 600

sec

45

GAS_FOD

17

HT.LO

Heating Lockout Temp

40 to 125

°F

75

OATLHEAT

21

SAT

15

SAT.H

SAT Heat Mode Sensing

Disable/En­
able

Disable

SAT_HEAT

16

SAM.L

Maximum SAT Lower
Level

85 to 200

°F

140

SATMAX_L

SAM.U

Maximum SAT Upper
Level

85 to 200

°F

160

SATMAX_H

SPT

Space Temperature

16

HT.PD

SPT Heat Demand (+)
Level

0.5 to 5

^F

1

HDEM_POS

HT.ND

SPT Heat Demand (­)
Level

­5 to ­0.5

^F

­1

HDEM_NEG

H.LAG

Heat Thermal Lag Factor

0 to 5

1

HEAT_LAG

48/50PG and PM