APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — CONFIGURATION (cont)
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT
PAGE NO.
COOL (cont)
Cooling Configuration
COOL_CFG
15
3.ON
Fan Lev3 On Temperature
0 to 100
°F
no HumidiMiZer FIOP:
65
HumidiMiZer FIOP:
88 (20, PM16)
68 (2428)(PG0316)
LEV3ON
3.OFF
Fan Lev3 Off Temperature
0 to 100
°F
no HumidiMiZer FIOP:
55
HumidiMiZer FIOP:
78 (20, PM16)
62 (2428)(PG0316)
LEV3OFF
HMZR
Humidimizer Config
HMZR_CFG
24
REHT
Humidimizer Equipped
No/Yes
No: no HumidiMiZer
FIOP
Yes: HumidiMiZer FIOP
REHEAT
24
R.DEC
Reheat2 Stage Decr.
Time
0 to 999
secs
60
RSTAGDEC
28
R.INC
Reheat2 Stage Incr. Time
0 to 999
secs
300
RSTAGINC
28
RH.FN
Reheat Fan Control
No/Yes
No (0314)
Yes (1628)
RHFANCTL
28
RF.LV
Reheat ODF Fan On
Level
0 to 3
2 (0320)
3 (2428)
RHFANLEV
28
RF. ON
Reheat ODF Fan On
Temp
0 to 100
°F
75 (PG0316)
93 (PG2024)(PM1628)
85 (PG 28)
RHFANON
28
RF.OF
Reheat ODF Fan Off
Temp
0 to 100
°F
70 (PG0316)
83 (20, PM16)
88 (24)(PM 28)
80 (PG 28)
RHFANOFF
28
RA.LO
Reheat2 OAT Limit A
20 to 70
°F
40
OATLRH_A
28
RA.LP
Reheat2 SSP Lo Limit A
50 to 100
psig
80
RHSSPL_A
28
RA.HP
Reheat2 SSP Hi Limit A
50 to 100
psig
90
RHSSPH_A
28
RB.LO
Reheat2 OAT Limit B,C
20 to 70
°F
50
OATLRH_B
28
RB.LP
Reheat2 SSP Lo Limit
B,C
50 to 100
psig
80
RHSSPL_B
28
RB.HP
Reheat2 SSP Hi Limit B,C
50 to 100
psig
90
RHSSPH_B
28
HEAT
Heating Configuration
HEAT_CFG
15
HT.TY
Type of Heat Installed
0=No Heat
1=Gas
2=Electric
0 (50 series with no elec
tric heat)
1 (48 series)
2 (50 series with electric
heat)
HEATTYPE
21
N.HTR
Number of Heat Stages
1 to 2
1 (48 series 1phase, 50
series <15kW)
2 (48 series 3phase, 50
series >=15kW)
NUM_HEAT
22
MRT.H
Heat Minimum On Time
60 to 999
sec
120
HMIN_ON
22
MOT.H
Heat Minimum Off Time
60 to 999
sec
120
HMIN_OFF
22
H.DEC
Heat Stage Decrease
Time
120 to 999
sec
300
HSTAGDEC
21
H.INC
Heat Stage Increase
Time
120 to 999
sec
450
HSTAGINC
21
FOD.E
Fanoff Delay, Elect Heat
10 to 600
sec
30
ELEC_FOD
17
FOD.G
Fanoff Delay, Gas Heat
45 to 600
sec
45
GAS_FOD
17
HT.LO
Heating Lockout Temp
40 to 125
°F
75
OATLHEAT
21
SAT
15
SAT.H
SAT Heat Mode Sensing
Disable/En
able
Disable
SAT_HEAT
16
SAM.L
Maximum SAT Lower
Level
85 to 200
°F
140
SATMAX_L
SAM.U
Maximum SAT Upper
Level
85 to 200
°F
160
SATMAX_H
SPT
Space Temperature
16
HT.PD
SPT Heat Demand (+)
Level
0.5 to 5
^F
1
HDEM_POS
HT.ND
SPT Heat Demand ()
Level
5 to 0.5
^F
1
HDEM_NEG
H.LAG
Heat Thermal Lag Factor
0 to 5
1
HEAT_LAG
48/50PG and PM