Carrier 48/50PM C16-28 User Manual
Page 168

168
Fan Performance — 50PM28 — Horizontal Supply/Return Units
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
6500
759
2.89
804
3.17
E
844
3.42
883
3.68
922
3.96
7000
E
810
3.47
E
853
3.77
891
4.04
F
928
4.30
F
964
4.58
7500
862
4.12
903
4.43
F
939
4.72
974
5.00
1008
5.29
8000
F
913
4.84
F
953
5.18
988
5.48
1021
5.77
1053
6.07
8500
965
5.63
1003
5.99
1037
6.32
G
1069
6.62
G
1100
6.93
9000
1017
6.50
1054
6.89
G
1087
7.23
1118
7.55
1147
7.87
9500
G
1069
7.45
G
1105
7.86
1137
8.22
1167
8.56
1195
8.89
10000
1121
8.48
1156
8.92
1187
9.30
1216
9.66
H
1243
10.01
10500
1173
9.60
H
1207
10.06
H
1238
10.47
H
1266
10.85
1292
11.21
11000
H
1226
10.81
1259
11.30
1288
11.72
1316
12.12
1342
12.50
11500
1278
12.11
1310
12.62
1339
13.07
1366
13.49
—
—
12000
1331
13.51
—
—
—
—
—
—
—
—
12500
—
—
—
—
—
—
—
—
—
—
Airflow
(Cfm)
Available External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
6500
962
4.27
F
1003
4.61
1045
4.98
1090
5.41
1135
5.87
7000
F
1000
4.88
1037
5.21
G
1075
5.56
G
1115
5.95
G
1155
6.38
7500
1041
5.58
G
1075
5.90
1110
6.24
1145
6.61
1182
7.01
8000
G
1085
6.37
1116
6.68
1148
7.01
1180
7.36
1214
7.74
8500
1129
7.23
1159
7.55
1189
7.88
H
1219
8.22
H
1249
8.59
9000
1175
8.18
1204
8.50
H
1232
8.83
1260
9.18
1288
9.53
9500
1222
9.22
H
1249
9.55
1276
9.88
1302
10.22
1329
10.58
10000
H
1270
10.34
1296
10.68
1321
11.02
1346
11.37
1371
11.72
10500
1318
11.56
1343
11.90
1367
12.25
1391
12.61
—
—
11000
1366
12.86
1390
13.22
—
—
—
—
—
—
11500
—
—
—
—
—
—
—
—
—
—
12000
—
—
—
—
—
—
—
—
—
—
12500
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp - Brake Horsepower Input to Fan
Boldface indicates field-supplied drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: 687-873, 5.75 Bhp
(F) Mid‐Low Range: 805 to 1007 rpm, 5.75 Bhp
(G) Mid‐High Range: 941 to 1176 rpm, 8.63 Bhp
(H) High Range: 1014 to 1297 rpm, 11.50 Bhp
All other rpms require field-supplied drive.
2. See General Fan Performance Notes.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Static pressure losses from accessories and options
(Humidi-MiZer
system, economizer, etc.) must be added
to external static pressure before entering Fan Performance
table. Refer to Accessory/FIOP Static Pressure information.
2. Extensive motor and drive testing on these units ensures
that the full horsepower range of the motor can be utilized
with confidence. Using the fan motors up to the bhp rating
shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. See
Evaporator−Fan Motor Specifications for additional
information.
3. Use of a field-supplied motor may affect wire size. Contact
your Carrier representative for details.
4. Interpolation is permissible. Do not extrapolate.
48/50PG and PM