APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — RUN STATUS (cont)

ITEM

EXPANSION

RANGE

UNITS

CCN TABLE/

SUB­TABLE

CCN POINT

CCN

WRITE

STATUS

MENU

WRITE

STATUS

HEAT

Heating Status

HEATDISP

DMD.H

Heating Demand

xxx.x

^F

HEAT_DMD

AVL.H

Available Heating Stages

x

AVLHSTGS

REQ.H

Requested Heating Stages

x

REQHSTGS

MAX.H

Max Allowed Heat Stages

x

MAXHSTGS

forcible

LMT.H

Max Heat Stage In Effect

x

HSTGLIMT

IDF

Indoor Fan State

Off/On

IDFSTATE

F.SPD

Commanded Fan Speed

xxx

%

FANSPEED

HT.1

Heat Stage 1 Relay

Off/On

HEAT_1

TG.H1

Heat Stage 1 Timeguard

xxx

sec

TIMGD_H1

HT.2

Heat Stage 2 Relay

Off/On

HEAT_2

TG.H2

Heat Stage 2 Timeguard

xxx

sec

TIMGD_H2

ECON

Economizer Status

ECONDISP

EC.CP

Econo Commanded Position

xxx

%

ECONOCMD

EC.AP

Econo Actual Position

xxx

%

ECONOPOS

EC.MP

Min Position in Effect

xxx

%

MIN_POS

forcible

IAQ.S

IAQ Level (switch)

Low/High

IAQIN

IAQ

IAQ Level (sensor)

xxxx

IAQ

OAT

Outdoor Air Temperature

xxx.x

°F

OA_TEMP

ENTH

Outdoor Enthalpy Switch

Low/High

ENTHALPY

OAQ

OAQ Level (sensor)

xxxx

OAQ

PE.1

Power Exhaust 1 Relay

Off/On

PE_1

PE.2

Power Exhaust 2 Relay

Off/On

PE_2

OAU

Outside Air Unit Status

OAUDISP

OA.RN

OAU System Run State

1=AUTO
2=OFF
3=TEST

OAU_RUN

OA.OP

OAU Operating Mode

0=Off
1=ERV (DCV)
2=Free Cooling
3=OA Tempering
4=Defrost
5=Test
6=Ext. Mode 1
7=Ext. Mode 2
8=Ext. Mode 3

OAU_MODE

UPC

UPC Software Version

xxxx

UPC_VER

OAU

OA Unit Software Version

xxxx

OAU_VER

2P.DM

OAU 2­position Damper

Close/Open

OAUDMPR

WHL

OAU Wheel Speed

xxx

%

OAUWHEEL

LAT

OAU Leaving Air Temp

xxx.x

°F

OAU_LAT

EXAT

OAU Exhaust Air Temp

xxx.x

°F

OAU_EXAT

OA.MN

Minimum Outside Air CFM

xxxxx

CFM

MINOACFM

DCV.M

Min DCV Outside Air CFM

xxxxx

CFM

MINDCVSP

OA.FS

OAU OA Fan Speed

xxx

%

OAFANSPD

A.OA

Actual Outside Air CFM

xxxxx

CFM

ACTOACFM

C.OA

Command Outside Air CFM

xxxxx

CFM

CMDOACFM

PE.OF

Power Exhaust CFM Offset

xxxxx

CFM

EXOFFSET

EX.FS

OAU Exhaust Fan Speed

xxx

%

OAUPESPD

A.EX

Actual Exhaust Air CFM

xxxxx

CFM

ACTEXCFM

C.EX

Command Exhaust Air CFM

xxxxx

CFM

CMDEXCFM

BP.SP

Building Pressure Setpnt

x.xx

in H2O

OAU_BPSP

BP

Building Pressure

x.xx

in H2O

OAU_BP

TM.LO

OA Tempring Lockout Temp

xx

°F

OATMPLOC

TM.SP

OA Tempring SAT Setpoint

xx

°F

OATMPSPT

OA.HT

OAU Tempering Heater

xxx

%

OAHEATER

HRS

Component Run Hours

STRTHOUR

A1

Compressor A1 Run Hours

xxxxx.xx

hours

HR_A1

forcible

A2

Compressor A2 Run Hours

xxxxx.xx

hours

HR_A2

forcible

B1

Compressor B1 Run Hours

xxxxx.xx

hours

HR_B1

forcible

C1

Compressor C1 Run Hours

xxxxx.xx

hours

HR_C1

forcible

CCH

Crankcase Heat Run Hours

xxxxx.xx

hours

HR_CCH

forcible

IDF

Indoor Fan Run Hours

xxxxx.xx

hours

HR_IDF

forcible

OFC.1

Outdoor Fan 1 Run Hours

xxxxx.xx

hours

HR_OFC_1

forcible

OFC.2

Outdoor Fan 2 Run Hours

xxxxx.xx

hours

HR_OFC_2

forcible

OFC.3

Outdoor Fan 3 Run Hours

xxxxx.xx

hours

HR_OFC_3

forcible

HT.1

Heat Stage 1 Run Hours

xxxxx.xx

hours

HR_HTR_1

forcible

HT.2

Heat Stage 2 Run Hours

xxxxx.xx

hours

HR_HTR_2

forcible

PE.1

Power Exhaust1 Run Hours

xxxxx.xx

hours

HR_PE_1

forcible

PE.2

Power Exhaust2 Run Hours

xxxxx.xx

hours

HR_PE_2

forcible

ALRM

Alarm Relay Run Hours

xxxxx.xx

hours

HR_ALM

forcible

CRC

Reheat1 Valve Run Hours

xxxxx.xx

hours

HR_CRC

forcible

RH2.A

Reheat2 Valve A Run Hrs

xxxxx.xx

hours

HR_RH2_A

forcible

RH2.B

Reheat2 Valve BC Run Hrs

xxxxx.xx

hours

HR_RH2_B

forcible

48/50PG and PM