APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — CONFIGURATION

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN TABLE/
SUB-TABLE

CCN POINT

PAGE NO.

CONFIGURATION

SERVICE
CONFIGURATION

14

DISP

Display Configuration

DISPLAY

14

METR

Metric Display

Off/On

Off

DISPUNIT

14

LANG

Language Selection

0=English
1=Spanish
2=French
3=Portuguese

0

LANGUAGE

14

PROT

Password Enable

Disable/Enable

Enable

PASS_EBL

14

PSWD

Service Password

0000 to 9999

1111

PASSWORD

14

TEST

Test Display LEDs

Off/On

Off

(display

only, not in table)

DISPTEST

14

UNIT

Unit Configuration

UNIT

14

S.DLY

Startup Delay

10 to 600

sec

30

STARTDLY

14

U.CTL

Unit Control Type

2=Thermostat
3=Space
Sensor

2

CTL_TYPE

14

T.CTL

Thermostat Control Type

0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital

0

STATTYPE

15

OC.FN

Fan On When Occupied

No/Yes

Yes

OCC_FAN

15

IDF.F

Shut Down on IDF Failure

No/Yes

Yes

FATALFAN

15

FN.SW

Fan Status Switch

0=No Switch
1=Normal
Open
2=Normal
Closed

0: no FIOP
1: FIOP

FANSTCFG

15

FL.SW

Filter Status Switch

0=No Switch
1=Normal
Open
2=Normal
Closed

0: no FIOP
1: FIOP

FILSTCFG

15

FS.SW

Fire Shutdown Switch

0=No Switch
1=Normal
Open
2=Normal
Closed

0: no FIOP
1: FIOP

SHTDNCFG

15

RM.SW

Remote Occupancy
Switch

0=No Switch
1=Normal
Open
2=Normal
Closed

0

REMOCCFG

15

SAT.T

SAT Settling Time

10 to 900

sec

240

SAT_SET

15

RAT.S

RAT Sensor on SPTO In­
put

No/Yes

No

RAT_SPTO

15

RH.S

RH Sensor on OAQ Input

No/Yes

No

RH_OAQ

15

RH.SW

Space Humidity Switch

0=No Switch
1=Normal
Open
2=Normal
Closed

0: no Humidi­MiZer
FIOP
1: Humidi­MiZer
FIOP

HUMSTCFG

15

TCS.C

Temp Cmp Strt Cool
Factr

0 to 60

mins

0

TCSTCOOL

15

TCS.H

Temp Cmp Strt Heat
Factr

0 to 60

mins

0

TCSTHEAT

15

48/50PG and PM