Appendix a — local display and ccn tables (cont), Mode — configuration – Carrier 48/50PM C16-28 User Manual
Page 100
![background image](/manuals/64998/100/background.png)
100
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — CONFIGURATION
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT
PAGE NO.
CONFIGURATION
SERVICE
CONFIGURATION
14
DISP
Display Configuration
DISPLAY
14
METR
Metric Display
Off/On
Off
DISPUNIT
14
LANG
Language Selection
0=English
1=Spanish
2=French
3=Portuguese
0
LANGUAGE
14
PROT
Password Enable
Disable/Enable
Enable
PASS_EBL
14
PSWD
Service Password
0000 to 9999
1111
PASSWORD
14
TEST
Test Display LEDs
Off/On
Off
(display
only, not in table)
DISPTEST
14
UNIT
Unit Configuration
UNIT
14
S.DLY
Startup Delay
10 to 600
sec
30
STARTDLY
14
U.CTL
Unit Control Type
2=Thermostat
3=Space
Sensor
2
CTL_TYPE
14
T.CTL
Thermostat Control Type
0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0
STATTYPE
15
OC.FN
Fan On When Occupied
No/Yes
Yes
OCC_FAN
15
IDF.F
Shut Down on IDF Failure
No/Yes
Yes
FATALFAN
15
FN.SW
Fan Status Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
FANSTCFG
15
FL.SW
Filter Status Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
FILSTCFG
15
FS.SW
Fire Shutdown Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
SHTDNCFG
15
RM.SW
Remote Occupancy
Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0
REMOCCFG
15
SAT.T
SAT Settling Time
10 to 900
sec
240
SAT_SET
15
RAT.S
RAT Sensor on SPTO In
put
No/Yes
No
RAT_SPTO
15
RH.S
RH Sensor on OAQ Input
No/Yes
No
RH_OAQ
15
RH.SW
Space Humidity Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0: no HumidiMiZer
FIOP
1: HumidiMiZer
FIOP
HUMSTCFG
15
TCS.C
Temp Cmp Strt Cool
Factr
0 to 60
mins
0
TCSTCOOL
15
TCS.H
Temp Cmp Strt Heat
Factr
0 to 60
mins
0
TCSTHEAT
15
48/50PG and PM