Appendix a — local display and ccn tables (cont), Mode — configuration (cont) – Carrier 48/50PM C16-28 User Manual
Page 101
101
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — CONFIGURATION (cont)
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT
PAGE NO.
COOL
Cooling Configuration
COOL_CFG
15
N.CIR
Number of Circuits
0 to 3
1 (0307)
2 (0814)
3 (PG16)
2 (2028, PM16)
NUM_CIRC
19
N.A
Compressors on Circuit A
1 to 2
1 (PG0324)
1 (PM(1628)
2 PG(28)
A_COMPS
19
MRT.C
Compressor Min On Time
120 to 999
sec
180
MIN_ON
19
MOT.C
Compressor Min Off Time
300 to 999
sec
300
MIN_OFF
19
RST.C
Runtime to Reset Strikes
120 to 999
sec
300
MIN_ON_S
37
C.DEC
Cool Stage Decrease
Time
120 to 999
sec
300
STAGEDEC
18
C.INC
Cool Stage Increase Time
120 to 999
sec
450
STAGEINC
18
FOD.C
Fanoff Delay, Mech Cool
0 to 600
sec
60
COOL_FOD
17
ALM.N
Alert Each Strike
No/Yes
Yes
ALM_NOW
37
SAT
Supply Air Temperature
21
SA.PD
SAT Cool Demand (+)
Level
0.5 to 10
^F
1
SAT_POS
SA.ND
SAT Cool Demand ()
Level
10 to 0.5
^F
1
SAT_NEG
SAT.U
Minimum SAT Upper
Level
35.0 to 65.0
°F
60 (PG0316)
58 (PG 2024)(PM
1628)
53 (PG 28)
SATMIN_H
SAT.L
Minimum SAT Lower
Level
35.0 to 65.0
°F
35 (0307)
45 (0814)
50 (PG16)
48 (2028, PM16)
SATMIN_L
SPT
Space Temperature
16
CL.PD
SPT Cool Demand (+)
Level
0.5 to 5
^F
1
DEM_POS
CL.ND
SPT Cool Demand ()
Level
5 to 0.5
^F
1
DEM_NEG
C.LAG
Cool Thermal Lag Factor
0 to 5
1
COOL_LAG
CIR.A
Circuit A
19
CA.LO
Circuit A Lockout Temp
0 to 100F
°F
0
OATLCMPA
CS.A1
Current Sensing A1
Disable/En
able
Disable (1phase)
Enable (3phase)
A1_SENSE
CS.A2
Current Sensing A2
Disable/En
able
Disable (0324)
Enable (PG 28)
A2_SENSE
A1.FN
Level 1 Fans A
0 to 7
no HumidiMiZer
FIOP:
1 (0324)(PM 28)
5 (PG 28)
HumidiMiZer FIOP:
0 (PG0316)
1 (2028, PM16)
CIR_A_1
A2.FN
Level 2 Fans A
0 to 7
no HumidiMiZer
FIOP:
0 (0307)
3 (0820)
2 (2428)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
3 (20, PM16)
2 (2428)
CIR_A_2
A3.FN
Level 3 Fans A
0 to 7
no HumidiMiZer
FIOP:
0 (0307)
3 (0824)(PM 28)
7 (PG 28)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
3 (2028, PM16)
CIR_A_3
CIR.B
Circuit B
CB.LO
Circuit B Lockout Temp
0 to 100F
°F
0: no HumidiMiZer
FIOP
HumidiMiZer FIOP:
40 (PG0816)
0 (2028,
PM16)(0307)
OATLCMPB
CS.B1
Current Sensing B1
Disable/En
able
Disable (0307)
Enable (0828)
B1_SENSE
B1.FN
Level 1 Fans B
0 to 7
no HumidiMiZer
FIOP:
0 (0307)
1 (PG0816)
4 (2028, PM16)
HumidiMiZer FIOP:
0 (PG0316)
1 (2028, PM16)
CIR_B_1
48/50PG and PM