APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN TABLE/
SUB-TABLE

CCN POINT

PAGE NO.

COOL

Cooling Configuration

COOL_CFG

15

N.CIR

Number of Circuits

0 to 3

1 (03­07)
2 (08­14)
3 (PG16)
2 (20­28, PM16)

NUM_CIRC

19

N.A

Compressors on Circuit A

1 to 2

1 (PG03­24)
1 (PM(16­28)
2 PG(28)

A_COMPS

19

MRT.C

Compressor Min On Time

120 to 999

sec

180

MIN_ON

19

MOT.C

Compressor Min Off Time

300 to 999

sec

300

MIN_OFF

19

RST.C

Runtime to Reset Strikes

120 to 999

sec

300

MIN_ON_S

37

C.DEC

Cool Stage Decrease
Time

120 to 999

sec

300

STAGEDEC

18

C.INC

Cool Stage Increase Time

120 to 999

sec

450

STAGEINC

18

FOD.C

Fan­off Delay, Mech Cool

0 to 600

sec

60

COOL_FOD

17

ALM.N

Alert Each Strike

No/Yes

Yes

ALM_NOW

37

SAT

Supply Air Temperature

21

SA.PD

SAT Cool Demand (+)
Level

0.5 to 10

^F

1

SAT_POS

SA.ND

SAT Cool Demand (­)
Level

­10 to ­0.5

^F

­1

SAT_NEG

SAT.U

Minimum SAT Upper
Level

35.0 to 65.0

°F

60 (PG03­16)
58 (PG 20­24)(PM
16­28)
53 (PG 28)

SATMIN_H

SAT.L

Minimum SAT Lower
Level

35.0 to 65.0

°F

35 (03­07)
45 (08­14)
50 (PG16)
48 (20­28, PM16)

SATMIN_L

SPT

Space Temperature

16

CL.PD

SPT Cool Demand (+)
Level

0.5 to 5

^F

1

DEM_POS

CL.ND

SPT Cool Demand (­)
Level

­5 to ­0.5

^F

­1

DEM_NEG

C.LAG

Cool Thermal Lag Factor

0 to 5

1

COOL_LAG

CIR.A

Circuit A

19

CA.LO

Circuit A Lockout Temp

0 to 100F

°F

0

OATLCMPA

CS.A1

Current Sensing A1

Disable/En­
able

Disable (1­phase)
Enable (3­phase)

A1_SENSE

CS.A2

Current Sensing A2

Disable/En­
able

Disable (03­24)
Enable (PG 28)

A2_SENSE

A1.FN

Level 1 Fans A

0 to 7

no Humidi­MiZer
FIOP:
1 (03­24)(PM 28)
5 (PG 28)
Humidi­MiZer FIOP:
0 (PG03­16)
1 (20­28, PM16)

CIR_A_1

A2.FN

Level 2 Fans A

0 to 7

no Humidi­MiZer
FIOP:
0 (03­07)
3 (08­20)
2 (24­28)
Humidi­MiZer FIOP:
0 (03­14)
1 (PG16)
3 (20, PM16)
2 (24­28)

CIR_A_2

A3.FN

Level 3 Fans A

0 to 7

no Humidi­MiZer
FIOP:
0 (03­07)
3 (08­24)(PM 28)
7 (PG 28)
Humidi­MiZer FIOP:
0 (03­14)
1 (PG16)
3 (20­28, PM16)

CIR_A_3

CIR.B

Circuit B

CB.LO

Circuit B Lockout Temp

0 to 100F

°F

0: no Humidi­MiZer
FIOP
Humidi­MiZer FIOP:
40 (PG08­16)
0 (20­28,
PM16)(03­07)

OATLCMPB

CS.B1

Current Sensing B1

Disable/En­
able

Disable (03­07)
Enable (08­28)

B1_SENSE

B1.FN

Level 1 Fans B

0 to 7

no Humidi­MiZer
FIOP:
0 (03­07)
1 (PG08­16)
4 (20­28, PM16)
Humidi­MiZer FIOP:
0 (PG03­16)
1 (20­28, PM16)

CIR_B_1

48/50PG and PM