A.FAN

Adaptive Fan

AFAN_CFG

34

AF.EN

Adaptive Fan Operation

No/Yes

No

ADAPTFAN

34

FS.VN

Fan Speed ­ Ventilation

0 to 100

%

50

FSPDVENT

34

FS.AQ

Fan Speed ­ IAQ Over­
ride

0 to 100

%

50

FSPDAQOR

34

FS.E1

Fan Speed ­ Free Cool
Lo

0 to 100

%

60

FSPDECO1

34

FS.E2

Fan Speed ­ Free Cool
Hi

0 to 100

%

90

FSPDECO2

34

FS.CL

Fan Speed ­ Mech Cool­
ing

60 to 100

%

100

FSPDCOOL

34

FS.HT

Fan Speed ­ Heating

65 to 100

%

100

FSPDHEAT

34

FS.RH

Fan Speed ­ Reheat2

65 to 100

%

100

FSPDREHT

34

ALM.O

Alarm Relay Config.

ALM_CFG

37

A.SPC

SPT/SPRH Sensor Fail­
ure

No/Yes

Yes

SPACE_AL

106

A.SRT

SAT/RAT Sensor Failure

No/Yes

Yes

SATRATAL

106

A.OAT

OAT Thermistor Failure

No/Yes

Yes

OAT_AL

106

A.CS

Current Sensor Failure

No/Yes

Yes

CS_AL

105

A.CMP

Compressor Failure

No/Yes

Yes

COMP_AL

106

A.CKT

Refrig Circuit Failure

No/Yes

Yes

CKT_AL

106

A.SSP

SSP Transducer Failure

No/Yes

Yes

SSP_AL

106

A.SCT

SCT Thermistor Failure

No/Yes

Yes

SCT_AL

106

A.FAN

Indoor Fan Failure

No/Yes

Yes

FAN_AL

106

A.FIL

Dirty Filter

No/Yes

Yes

FILT_AL

106

A.TST

Thermostat Failure

No/Yes

Yes

TSTAT_AL

106

A.ECO

Economizer Failure

No/Yes

Yes

ECON_AL

106

PID

PID Configurations

PID_CFG

37

EC.P

Economizer PID ­ kP

0.00 to 99.90

2.5

ECONO_P

106

EC.I

Economizer PID ­ kI

0.00 to 99.90

0.12

ECONO_I

106

EC.D

Economizer PID ­ kD

0.00 to 99.90

1

ECONO_D

106

EC.DT

Economizer PID ­ rate

10.00 to 180.00

secs

15

ECONO_DT

106

EC.DB

Economizer PID Dead­
band

0 to 25

%

3

ECONBAND

106

LK.P

Linkage Staging PID ­ kP

0.00 to 99.90

10

LINK_P

106

LK.I

Linkage Staging PID ­ kI

0.00 to 99.90

5

LINK_I

106

LK.D

Linkage Staging PID ­
kD

0.00 to 99.90

5

LINK_D

106

LK.DT

Linkage Staging PID ­
rate

10.00 to 180.00

secs

30

LINK_DT

106

(GENERIC = CCN

only)

GENERICS

96

POINT 01 Definition

Point_01

POINT 02 Definition

Point_02

POINT 03 Definition

Point_03

POINT 04 Definition

Point_04

POINT 05 Definition

Point_05

POINT 06 Definition

Point_06

POINT 07 Definition

Point_07

POINT 08 Definition

Point_08

POINT 09 Definition

Point_09

POINT 10 Definition

Point_10

POINT 11 Definition

Point_11

POINT 12 Definition

Point_12

POINT 13 Definition

Point_13

POINT 14 Definition

Point_14

POINT 15 Definition

Point_15

POINT 16 Definition

Point_16

POINT 17 Definition

Point_17

POINT 18 Definition

Point_18

POINT 19 Definition

Point_19

POINT 20 Definition

Point_20

TRIM

Sensor Calibration

(CCN TRIM ­ see

Maintenance Dis­
play)

5

SPT.C

Space Temp Calibration

­30 to 130

°F

52

SPT.T

Space Temp Trim

­30 to 30

^F

0

52

SAT.C

Supply Air Temp Calib.

­30 to 130

°F

52

SAT.T

Supply Air Temp Trim

­30 to 30

^F

0

15

RAT.C

Return Air Temp Calib.

­30 to 130

°F

106

RAT.T

Return Air Temp Trim

­30 to 30

^F

0

106

CCN
CONFIGURATION

CCN

CCN Configuration

4850PGPM

17

CCN.A

CCN Element Number

1 to 239

1

CCNADD

35

CCN.B

CCN Bus Number

0 to 239

0

CCNBUS

35

BAUD

CCN Baud Rate

1=2400
2=4800
3=9600
4=19200
5=38400

3

CCNBAUDD

35

48/50PG and PM