Table 12 — ComfortLink

t Alarm Codes (cont)

ALARM

OR

ALERT

NUMBER

DESCRIPTION

ACTION TAKEN BY

CONTROL

RESET

METHOD

PROBABLE CAUSE

A154

Serial EEPROM Hardware Failure

Unit Shutdown

Automatic

Software failure or MBB failure

T155

Serial EEPROM Storage Failure Error

Unit operation errors

Automatic

Software failure or MBB failure

A156

Critical Serial EEPROM Storage Fail Error

Unit Shutdown

Automatic

Software failure or MBB failure

A157

A/D Hardware Failure

Unit Shutdown

Automatic

Software failure or MBB failure

A163

Circuit A Down Due to Failure

Lockout Circuit A

Manual

Circuit has 3 strikes or has been locked out by another alarm

Service Test - Circuit A Down Due to Failure

A164

Circuit B Down Due to Failure

Lockout Circuit B

Manual

Circuit has 3 strikes or has been locked out by another alarm

Service Test - Circuit B Down Due to Failure

A165

Circuit C Down Due to Failure

Lockout Circuit C

Manual

Circuit has 3 strikes or has been locked out by another alarm

Service Test - Circuit C Down Due to Failure

T173

Loss of communication with the Energy
Management Module

No action

Automatic

MBB Software failure, reload software or replace board

T179

Loss of communication with the Economizer
Control Board

No economizer operation

Automatic

Communication wiring problem with ECB or faulty MBB or ECB

T180

Loss of communication with the Economizer
Actuator

No economizer operation

Automatic

Communication wiring problem with actuator.

T181

Loss of communication with Outside Air Unit

Reset OAU data

Automatic

Wiring Problem or OAU communication failure

A200

Linkage Timeout Error - Comm Failure

No Linkage Operation fall

back to local SPT

Automatic

Received a table write from Linkage before, now not receiving
any linkage commands

A404

Fire Shutdown

Unit Shutdown

Automatic

Smoke detected by smoke detector

T408

Dirty Air Filter

Alert Generated

Automatic

Dirty Filter

T409

Fan Status Switch ON, fan commanded off

If IDF.F = Yes, then Unit

Shutdown

If IDF.F =

YES, then

Manual,

otherwise

automatic

Bad Fan Status Switch. Configuration incorrect.

Fan Status Switch OFF, fan commanded on

If IDF.F = Yes, then Unit

Shutdown

If IDF.F =

YES, then

Manual,

otherwise

automatic

Tripped Circuit Breaker. Broken belt. Bad indoor fan motor.
Configuration incorrect. Bad fan status switch.

T410

R-W1 Jumper Not Installed in Space Temp Mode

Unable to run heat

Automatic

Missing jumper wire

R-W1 Jumper Must Be Installed to Run Heat In
Service Test

Unable to Test Heat Outputs

Automatic

Missing jumper wire

T411

Thermostat Y2 Input Activated without Y1 Activated

Run unit as if Y2 and Y1 are

On

Automatic

Bad Thermostat or Thermostat Wiring

T412

Thermostat W2 Input Activated without W1
Activated

Run unit as if W2 and W1 are

On

Automatic

Bad Thermostat or Thermostat Wiring

T413

Thermostat Y and W Inputs Activated
Simultaneously

Run unit in mode activated

first

Automatic

Bad Thermostat or Thermostat Wiring

T414

Economizer Damper Actuator Out of Calibration

Alert Generated

Automatic

Calibrate economizer (E.CAL). If problem still exist then
determine what is limiting economizer rotation.

Economizer Damper Actuator Torque Above Load
Limit

Alert Generated

Automatic

Actuator load too high. Check damper load.

Economizer Damper Actuator Hunting Excessively

Alert Generated

Automatic

Damper position changing too quickly.

Economizer Damper Stuck or Jammed

Alert Generated

Automatic

No economizer motion. Check damper blades, gears, and
actuator.

Economizer Damper Actuator Mechanical Failure

Alert Generated

Automatic

Check actuator and replace if necessary.

Economizer Damper Actuator Direction Switch
Wrong

Alert Generated

Automatic

Actuator direction control switch (CCW, CW) wrong.

T415

IAQ Input Out of Range

No IAQ Operations

Automatic

Bad sensor, bad wiring, or sensor configured incorrectly.

T416

OAQ Input Out of Range

No OAQ Operations

Automatic

Bad sensor, bad wiring, or sensor configured incorrectly.

T418

OAU Motor Failure

Alert generated

Automatic

Check OAU motors for failure

OAU Dirty Filter

Alert generated

Automatic

Check/change OAU filters

OAU Low CFM

Alert generated

Automatic

Check OAU air flow

OAU General Alarm

Alert generated

Automatic

Check OAU

LEGEND
ECB

-

Economizer Control Board

IGC

-

Integrated Gas Controller

MBB

-

Main Base Board

OAT

-

Outdoor-Air Thermistor