42 table 12 — comfort link t alarm codes (cont), 48/50pg and pm – Carrier 48/50PM C16-28 User Manual
Page 42
![background image](/manuals/64998/42/background.png)
42
Table 12 — ComfortLink
t Alarm Codes (cont)
ALARM
OR
ALERT
NUMBER
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET
METHOD
PROBABLE CAUSE
A154
Serial EEPROM Hardware Failure
Unit Shutdown
Automatic
Software failure or MBB failure
T155
Serial EEPROM Storage Failure Error
Unit operation errors
Automatic
Software failure or MBB failure
A156
Critical Serial EEPROM Storage Fail Error
Unit Shutdown
Automatic
Software failure or MBB failure
A157
A/D Hardware Failure
Unit Shutdown
Automatic
Software failure or MBB failure
A163
Circuit A Down Due to Failure
Lockout Circuit A
Manual
Circuit has 3 strikes or has been locked out by another alarm
Service Test - Circuit A Down Due to Failure
A164
Circuit B Down Due to Failure
Lockout Circuit B
Manual
Circuit has 3 strikes or has been locked out by another alarm
Service Test - Circuit B Down Due to Failure
A165
Circuit C Down Due to Failure
Lockout Circuit C
Manual
Circuit has 3 strikes or has been locked out by another alarm
Service Test - Circuit C Down Due to Failure
T173
Loss of communication with the Energy
Management Module
No action
Automatic
MBB Software failure, reload software or replace board
T179
Loss of communication with the Economizer
Control Board
No economizer operation
Automatic
Communication wiring problem with ECB or faulty MBB or ECB
T180
Loss of communication with the Economizer
Actuator
No economizer operation
Automatic
Communication wiring problem with actuator.
T181
Loss of communication with Outside Air Unit
Reset OAU data
Automatic
Wiring Problem or OAU communication failure
A200
Linkage Timeout Error - Comm Failure
No Linkage Operation fall
back to local SPT
Automatic
Received a table write from Linkage before, now not receiving
any linkage commands
A404
Fire Shutdown
Unit Shutdown
Automatic
Smoke detected by smoke detector
T408
Dirty Air Filter
Alert Generated
Automatic
Dirty Filter
T409
Fan Status Switch ON, fan commanded off
If IDF.F = Yes, then Unit
Shutdown
If IDF.F =
YES, then
Manual,
otherwise
automatic
Bad Fan Status Switch. Configuration incorrect.
Fan Status Switch OFF, fan commanded on
If IDF.F = Yes, then Unit
Shutdown
If IDF.F =
YES, then
Manual,
otherwise
automatic
Tripped Circuit Breaker. Broken belt. Bad indoor fan motor.
Configuration incorrect. Bad fan status switch.
T410
R-W1 Jumper Not Installed in Space Temp Mode
Unable to run heat
Automatic
Missing jumper wire
R-W1 Jumper Must Be Installed to Run Heat In
Service Test
Unable to Test Heat Outputs
Automatic
Missing jumper wire
T411
Thermostat Y2 Input Activated without Y1 Activated
Run unit as if Y2 and Y1 are
On
Automatic
Bad Thermostat or Thermostat Wiring
T412
Thermostat W2 Input Activated without W1
Activated
Run unit as if W2 and W1 are
On
Automatic
Bad Thermostat or Thermostat Wiring
T413
Thermostat Y and W Inputs Activated
Simultaneously
Run unit in mode activated
first
Automatic
Bad Thermostat or Thermostat Wiring
T414
Economizer Damper Actuator Out of Calibration
Alert Generated
Automatic
Calibrate economizer (E.CAL). If problem still exist then
determine what is limiting economizer rotation.
Economizer Damper Actuator Torque Above Load
Limit
Alert Generated
Automatic
Actuator load too high. Check damper load.
Economizer Damper Actuator Hunting Excessively
Alert Generated
Automatic
Damper position changing too quickly.
Economizer Damper Stuck or Jammed
Alert Generated
Automatic
No economizer motion. Check damper blades, gears, and
actuator.
Economizer Damper Actuator Mechanical Failure
Alert Generated
Automatic
Check actuator and replace if necessary.
Economizer Damper Actuator Direction Switch
Wrong
Alert Generated
Automatic
Actuator direction control switch (CCW, CW) wrong.
T415
IAQ Input Out of Range
No IAQ Operations
Automatic
Bad sensor, bad wiring, or sensor configured incorrectly.
T416
OAQ Input Out of Range
No OAQ Operations
Automatic
Bad sensor, bad wiring, or sensor configured incorrectly.
T418
OAU Motor Failure
Alert generated
Automatic
Check OAU motors for failure
OAU Dirty Filter
Alert generated
Automatic
Check/change OAU filters
OAU Low CFM
Alert generated
Automatic
Check OAU air flow
OAU General Alarm
Alert generated
Automatic
Check OAU
LEGEND
ECB
-
Economizer Control Board
IGC
-
Integrated Gas Controller
MBB
-
Main Base Board
OAT
-
Outdoor-Air Thermistor
48/50PG and PM