beautypg.com

Carrier 48/50PM C16-28 User Manual

Page 10

background image

10

NOTE: On standard units, the fire shutdown input is the terminals
Fire Shutdown 1 and 2. On Humidi-MiZer

 units, the fire

shutdown connections are at PL19.

Outdoor Enthalpy

If an Outdoor Enthalpy accessory was field installed, the unit must
be configured for it by setting Configuration

ECONEN.SW,

identifies the normally open or normally closed status of this input
when the outdoor enthalpy is low.

IAQ Switch

If an IAQ Switch accessory was field installed, the unit must be
configured for it by setting Configuration

AIR.QII.CF,

identifies the normally open or normally closed status of this input
when the indoor air quality value is low (good) and also selects the
unit response to this input.

NOTE: An IAQ switch cannot be used if an enthalpy switch is
already on this input.

IAQ Sensor

If an CO

2

Sensor accessory was field installed, the unit must be

configured for it by setting Configuration

AIR.QIA.CF

selects the unit response to this input. Default conversion to 0 to
2000 ppm.

OAQ Sensor

If an Outdoor Air Quality Sensor accessory was field installed, the
unit must be configured for it by setting Configuration

AIR.Q

OA.CF selects the unit response to this input. Default
conversion to 0 to 2000 ppm.

Fan Status

If a Fan Status accessory was field installed, the unit must be
configured for it by setting Configuration

UNITFN.SW to

normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.

NOTE: Fan Status input is not on the terminals marked Fan
Status.

Filter Status

If a Filter Status accessory was field installed, the unit must be
configured for it by setting Configuration

UNITFL.SW to

normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.

Programming Operating Schedules

The ComfortLink

t controls will accommodate up to eight

different schedules (Periods 1 through 8), and each schedule is
assigned to the desired days of the week. Each schedule includes
an occupied on and off time. As an example, to set an occupied
schedule for 8 AM to 5 PM for Monday through Friday, the user
would set days Monday through Friday to ON for Period 1. Then
the user would configure the Period 1 Occupied From point to
08:00 and the Period 1 Occupied To point to 17:00. To create a
different weekend schedule, the user would use Period 2 and set
days Saturday and Sunday to ON with the desired Occupied On
and Off times.

NOTE: By default, the time schedule periods are programmed for
24 hours of occupied operation.

To create a schedule, perform the following procedure:

1. Scroll to the Configuration mode, and select CCN

CONFIGURATION (CCN). Scroll down to the Schedule
Number (Configuration

CCNSCH.O=SCH.N). If

password protection has been enabled, the user will be
prompted to enter the password before any new data is
accepted. SCH.N has a range of 0 to 99. The default value
is 1. A value of 0 is always occupied, and the unit will
control to its occupied set points. A value of 1 means the
unit will follow a local schedule, and a value of 65 to 99
means it will follow a CCN schedule. Schedules 2−64 are
not used as the control only supports one internal/local
schedule. If one of the 2−64 schedules is configured, then
the control will force the number back to 1. Make sure the
value is set to 1 to use a local schedule.

2. Enter the Time Clock mode. Scroll down to the LOCAL

TIME SCHEDULE (SCH.L) sub−mode, and press
ENTER. Period 1 (PER.1) will be displayed.

3. Scroll down to the MON.1 point. This point indicates if

schedule 1 applies to Monday. Use the ENTER command
to go into Edit mode, and use the Up or Down key to
change the display to YES or NO. Scroll down through the
rest of the days and apply schedule 1 where desired. The
schedule can also be applied to a holiday.

4. Configure the beginning of the occupied time period for

Period 1 (OCC). Press ENTER to go into Edit mode, and
the first two digits of the 00.00 will start flashing. Use the
Up or Down key to display the correct value for hours, in
24−hour (military) time. Press ENTER and hour value is
saved and the minutes digits will start flashing. Use the
same procedure to display and save the desired minutes
value.

5. Configure the unoccupied time for period 1 (UNC). Press

ENTER to go into Edit mode, and the first two digits of the
00.00 will start flashing. Use the Up or Down key to display
the correct value for hours, in 24−hour (military) time. Press
ENTER and hour value is saved and the minutes digits will
start flashing. Use the same procedure to display and save
the desired minutes value.

6. The first schedule is now complete. If a second schedule is

needed, such as for weekends or holidays, scroll down and
repeat the entire procedure for period 2 (PER.2). If
additional schedules are needed, repeat the process for as
many as are needed. Eight schedules are provided. See
Table 3 for an example of setting the schedule.

48/50PG and PM

This manual is related to the following products: