APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — TIME CLOCK
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT
TIME CLOCK
CONFIGURATION
TIME
Time of Day
TIME
TIME
Hour and Minute
xx.xx
hh.mm
TIME
DATE
Current Date
MNTH
Month of Year
January, February, ...,
December
MOY
DOM
Day of Month
1 to 31
DOM
YEAR
Year
xxxx
YOCDISP
DAY
Day of Week
Monday, Tuesday, ...,
Sunday
DOWDISP
DST
Daylight Savings Config.
BRODEFS (continued)
STR.M
Start Month
January, February, ...,
December
4
STARTM
STR.W
Start Week
1 to 5
1
STARTW
STR.D
Start Day
1 to 7
7
STARTD
M.ADD
Minutes to Add
0 to 90
60
MINADD
STP.M
Stop Month
January, February, ...,
December
10
STOPM
STP.W
Stop Week
1 to 5
5
STOPW
STP.D
Stop Day
1 to 7
7
STOPD
M.SUB
Minutes to Subtract
0 to 90
60
MINSUB
SCH.L
Occupancy Schedule
(SCH.L = Display only)
PER.x
Occupancy Period x
OCC.x
Occupied From
00.00 to 23.59
hh.mm
00.00
PERxOCC
UNC.x
Occupied To
00.00 to 23.60
hh.mm
00.00
PERxUNC
MON.x
Monday in Period
Yes/No
No
PERxMON
TUE.x
Tuesday in Period
Yes/No
No
PERxTUE
WED.x
Wednesday in Period
Yes/No
No
PERxWED
THU.x
Thursday in Period
Yes/No
No
PERxTHU
FRI.x
Friday in Period
Yes/No
No
PERxFRI
SAT.x
Saturday in Period
Yes/No
No
PERxSAT
SUN.x
Sunday in Period
Yes/No
No
PERxSUN
HOL.x
Holiday in Period
Yes/No
No
PERxHOL
(repeat up to x=8
Periods)
(OCCFECS = CCN only)
OCCDEFCS
Timed Override Hours
x
hours
OVREXT
Period x DOW
(MTWTFSSH)
xxxxxxxx
00000000
DOWx
Occupied From
00.00 to 24.00
hh.mm
00.00
OCCTODx
Occupied To
00.00 to 24.00
hh.mm
00.00
UNOCTODx
(repeat up to x=8
Periods)
HOL.L
Holiday Schedule
HOLIDAY
HOL.x
Holiday x
HOLDYxxS
MON.x
Holiday Start Month
1 to 12 = January to
December
0
HOLMONxx
DAY.x
Holiday Start Day
1 to 31
0
HOLDAYxx
LEN.x
Holiday Duration (days)
1 to 99
0
HOLLENxx
(repeat up to x=9 Hol
idays)
(repeat up to
xx=30 Holidays)
CCN ONLY TABLES
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT
(ALARMDEF = CCN only)
ALARMDEF
Alarm Routing Control
00000000 to 11111111
11000000
ALRM_CNT
Equipment Priority
0 to 7
5
EQP_TYPE
Comm Failure Retry Time
1 to 240
min
10
RETRY_TM
Re-Alarm Time
1 to 255
min
180
RE-ALARM
Alarm System Name
up to 8 alphanum
4850PGPM
ALRM_NAM
(CTLRID = CCN only)
CTLR-ID
Device Name:
4850PGPM
Description:
text string
Location:
text string
Software Part Number:
CESR131320-XX-XX
Model Number:
Serial Number:
Reference Number:
48/50PG and PM