48/50pg and pm – Carrier 48/50PM C16-28 User Manual
Page 152
152
Fan Performance — 48PMD20 Vertical Supply/Return Units
CFM
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
5400
582
1.23
A
645
1.47
A
704
1.72
A
763
2.00
A
823
2.32
A
886
2.71
A
5700
605
1.42
A
666
1.67
A
723
1.93
A
779
2.21
A
835
2.52
A
893
2.89
A
6000
629
1.62
A
688
1.88
A
743
2.15
A
796
2.44
A
848
2.75
A
902
3.10
A
6300
653
1.83
A
710
2.12
A
763
2.40
A
814
2.69
A
864
3.00
A
914
3.35
A
6600
677
2.07
A
732
2.37
A
784
2.66
A
833
2.96
A
880
3.28
A
928
3.62
A
6900
701
2.33
A
755
2.64
A
805
2.95
A
852
3.26
A
898
3.58
A
944
3.92
A
7200
726
2.61
A
777
2.94
A
826
3.26
A
872
3.58
A
917
3.91
A
960
4.25
A
7500
750
2.92
A
800
3.25
A
848
3.59
A
893
3.92
A
936
4.26
B
978
4.61
B
7800
775
3.24
A
824
3.60
A
870
3.94
A
913
4.29
B
955
4.64
B
996
5.00
B
8100
800
3.59
A
847
3.96
A
892
4.32
B
935
4.68
B
975
5.04
B
1015
5.41
B
8400
825
3.97
A
871
4.35
B
914
4.73
B
956
5.10
B
996
5.48
B
1035
5.85
C
8700
850
4.38
B
894
4.77
B
937
5.16
B
978
5.55
B
1017
5.93
C
1055
6.32
C
9000
875
4.81
B
918
5.21
B
960
5.62
B
1000
6.02
C
1038
6.42
C
1075
6.82
C
CFM
Available External Static Pressure (in. wg)
1.4
1.6
1.8
2.0
2.2
2.4
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
5400
950
3.16
A
1013
3.66
A
1071
4.17
A
1123
4.67
B
1167
5.14
B
1207
5.57
B
5700
953
3.32
A
1014
3.81
A
1073
4.34
B
1128
4.88
B
1177
5.41
B
1221
5.90
C
6000
958
3.51
A
1016
3.98
A
1074
4.50
B
1130
5.06
B
1182
5.63
B
1230
6.19
C
6300
966
3.74
A
1020
4.18
A
1075
4.69
B
1130
5.24
B
1184
5.83
C
1234
6.43
C
6600
977
4.00
A
1027
4.43
B
1079
4.91
B
1132
5.44
B
1184
6.03
C
1236
6.65
C
6900
990
4.30
B
1037
4.71
B
1085
5.17
B
1135
5.68
B
1185
6.25
C
1236
6.86
C
7200
1004
4.63
B
1049
5.03
B
1094
5.47
B
1141
5.96
C
1188
6.51
C
1237
7.10
C
7500
1020
4.98
B
1062
5.38
B
1105
5.82
C
1149
6.29
C
1194
6.81
C
1240
7.38
C
7800
1037
5.37
B
1077
5.77
C
1118
6.20
C
1160
6.66
C
1202
7.16
C
1245
7.70
C
8100
1054
5.79
C
1093
6.19
C
1132
6.61
C
1172
7.07
C
1212
7.55
C
1253
8.08
C
8400
1073
6.24
C
1110
6.64
C
1148
7.07
C
1186
7.51
C
1224
7.99
C
1263
8.50
C
8700
1092
6.72
C
1128
7.13
C
1164
7.55
C
1201
8.00
C
1237
8.47
C
1274
8.97
D
9000
1111
7.22
C
1146
7.64
C
1181
8.07
C
1216
8.51
C
1252
8.98
D
1287
9.48
D
LEGEND
Bhp - Brake Horsepower Input to Fan
Rpm - Fan speed
Drive - Drive option code based on 460V motor max BHP
Grey cells indicate field supplied pulley change required.
Fan Performance — 48PME20 and 48PMF20 — Vertical Supply/Return Units
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
CFM
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
5400
599
1.30
A
661
1.54
A
720
1.79
A
779
2.08
A
839
2.42
A
903
2.82
A
5700
623
1.49
A
683
1.74
A
739
2.00
A
795
2.29
A
851
2.62
A
910
3.01
A
6000
648
1.70
A
706
1.97
A
760
2.24
A
812
2.53
A
865
2.85
A
920
3.22
A
6300
673
1.93
A
729
2.21
A
781
2.49
A
831
2.79
A
881
3.11
A
932
3.47
A
6600
698
2.18
A
752
2.48
A
802
2.77
A
851
3.08
A
898
3.40
A
946
3.76
A
6900
723
2.46
A
775
2.77
A
824
3.07
A
871
3.39
A
917
3.72
A
962
4.07
A
7200
749
2.75
A
799
3.08
A
846
3.40
A
892
3.72
A
936
4.06
A
980
4.41
B
7500
774
3.08
A
823
3.41
A
869
3.74
A
913
4.08
A
956
4.42
B
998
4.78
B
7800
800
3.42
A
847
3.77
A
892
4.12
A
935
4.47
B
976
4.82
B
1017
5.19
B
8100
826
3.79
A
871
4.16
A
915
4.52
B
957
4.88
B
997
5.24
B
1036
5.62
B
8400
851
4.19
A
896
4.57
B
939
4.94
B
979
5.32
B
1018
5.69
B
1057
6.07
C
8700
877
4.62
B
921
5.01
B
962
5.40
B
1002
5.78
C
1040
6.17
C
1077
6.56
C
9000
904
5.07
B
946
5.48
B
986
5.88
C
1025
6.28
C
1062
6.68
C
1098
7.08
C
CFM
Available External Static Pressure (in. wg)
1.4
1.6
1.8
2.0
2.2
2.4
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
RPM
BHP
Drive
5400
967
3.29
A
1029
3.80
A
1086
4.31
B
1135
4.79
B
1178
5.25
B
1216
5.68
B
5700
971
3.45
A
1031
3.96
A
1090
4.50
B
1143
5.03
B
1191
5.55
B
1233
6.04
C
6000
976
3.65
A
1034
4.14
A
1092
4.68
B
1147
5.24
B
1198
5.81
C
1244
6.36
C
6300
985
3.88
A
1039
4.35
B
1094
4.87
B
1149
5.44
B
1202
6.04
C
1251
6.64
C
6600
996
4.15
A
1046
4.60
B
1099
5.10
B
1151
5.66
B
1204
6.26
C
1254
6.88
C
6900
1009
4.46
B
1056
4.89
B
1105
5.37
B
1155
5.90
C
1206
6.49
C
1256
7.12
C
7200
1024
4.80
B
1069
5.22
B
1114
5.68
B
1162
6.19
C
1210
6.76
C
1258
7.37
C
7500
1040
5.17
B
1082
5.58
B
1126
6.03
C
1170
6.53
C
1215
7.07
C
1262
7.66
C
7800
1057
5.57
B
1098
5.98
C
1139
6.42
C
1181
6.90
C
1224
7.43
C
1267
8.00
C
8100
1075
6.01
C
1114
6.42
C
1154
6.85
C
1193
7.32
C
1234
7.83
C
1275
8.38
C
8400
1094
6.47
C
1132
6.88
C
1170
7.32
C
1208
7.78
C
1246
8.28
C
1285
8.81
D
8700
1114
6.97
C
1150
7.38
C
1187
7.82
C
1223
8.28
C
1260
8.77
D
1297
9.29
D
9000
1134
7.50
C
1169
7.92
C
1204
8.36
C
1239
8.82
D
1275
9.30
D
1310
9.81
D
LEGEND
Bhp - Brake Horsepower Input to Fan
Rpm - Fan speed
Drive - Drive option code based on 460V motor max BHP
Grey cells indicate field supplied pulley change required.