APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

RANGE

UNITS

DEFAULT

CCN TABLE/
SUB-TABLE

CCN POINT

PAGE NO.

ECON

Economizer Configuration

ECON_CFG

23

EC.EN

Economizer Installed

No/Yes

No: no FIOP
Yes: FIOP

ECONO

23

E.CTL

Economizer Control Type

1=Dig/Posi­
tion
2=Dig/Com­
mand
3=Analog
Ctrl

1

ECON_CTL

14

EC.MN

Econo Minimum Position

0 to 100

%

30
0: ERV FIOP

ECONOMIN

23

EC.MX

Econo Cool Max Position

0 to 100

%

100

ECONOMAX

23

M.ANG

Min Actuator Ctrl Angle

75 to 90

88

MINANGLE

23

EH.LO

Econo Cool Hi Temp Limit

40 to 100

°F

65

OATLECLH

23

EL.LO

Econo Cool Lo Temp
Limit

­30 to 50

°F

0

OATLECLL

23

DF.DB

Diff Dry Bulb Control

Disable/En­
able

Disable

DIFFBULB

23

UEFC

Unoccupied Free Cooling

0=Disabled
1=Unoc­
cpied
2=PreOccu­
pancy

2

UEFC_CFG

23

FC.TM

Free Cool PreOcc Time

1 to 9999

mins

120

UEFCTIME

23

FC.LO

Free Cool Low Temp Limit

­30 to 70

°F

50

OATLUEFC

23

PE.EN

Power Exhaust Installed

No/Yes

No: no FIOP
Yes: FIOP

PE_ENABL

24

PE.1

PE Stage1 Econo Position

0 to 100

%

40

PE1_POS

24

PE.2

PE Stage2 Econo Position

0 to 100

%

75

PE2_POS

24

EN.SW

Enthalpy Switch

0=No Switch
1=Normal
Open
2=Normal
Closed

0: no FIOP
1: FIOP

ENTHLCFG

10

E.TRV

Economizer Travel Time

5 to 300

secs

150

ECONOTRV

104

E.MXB

Bottom Stage Max Econo

0 to 100

%

50

ECONMAXB

104

E.MXM

Middle Stage Max Econo

0 to 100

%

35

ECONMAXM

104

E.MXT

Top Stage Max Econo

0 to 100

%

25 (PG03­16)
0 (20­28, PM16)

ECONMAXT

104

AIR.Q

Air Quality Config.

IAQ_CFG

14

IA.CF

IAQ Analog Input Config

0=No IAQ
1=DCV
2=Override
IAQ
3=Ctrl Min
Pos

0: no FIOP
1: FIOP

IAQANCFG

14

IA.FN

IAQ Analog Fan Config

0=Never
1=Occupied
2=Always

0

IAQANFAN

30

II.CF

IAQ Switch Input Config

0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override
N/O
4=Override
N/C

0

IAQINCFG

30

II.FN

IAQ Switch Fan Config

0=Never
1=Occupied
2=Always

0

IAQINFAN

34

AQ.MN

Econo Min IAQ Position

0 to 100

%

10
0: ERV FIOP

IAQMINP

30

EC.MN

Econo Minimum Position

0 to 100

%

30
0: ERV FIOP

ECONOMIN

23

OVR.P

IAQ Override Position

0 to 100

%

100

IAQOVPOS

30

OA.CF

OAQ Analog Input Config

0=No OAQ
1=DCV
2=Lockout
OAQ

0

OAQANCFG

30

OAQ.L

OAQ Lockout Limit

0 to 5000

600

OAQLOCK

30

AQD.L

AQ Differential Low

0 to 5000

100

DAQ_LOW

30

AQD.H

AQ Differential High

0 to 5000

700

DAQ_HIGH

30

DF.ON

Fan On AQ Differential

0 to 5000

600

DAQFNON

34

DF.OF

Fan Off AQ Differential

0 to 5000

200

DAQFNOFF

34

I.4M

IAQ Sensor Value at 4mA

0 to 5000

0

IAQ_4MA

30

I.20M

IAQ Sensor Value at
20mA

0 to 5000

2000

IAQ_20MA

30

O.4M

OAQ Sensor Value at
4mA

0 to 5000

0

OAQ_4MA

33

O.20M

OAQ Sensor Value at
20mA

0 to 5000

2000

OAQ_20MA

33

H.4M

RH Sensor Value at 4mA

0 to 50

%

0

RH_4MA

24

H.20M

RH Sensor Value at 20mA

60 to 100

%

100

RH_20MA

24

48/50PG and PM