APPENDIX D — ADDITIONAL START−UP DATA
Air Quantity Limits (50PG03−14 Units)
UNIT
50PG
COOLING (cfm)
HEATING (cfm)
OPTIONAL ELECTRIC HEAT
Min
Max
Min
Max
03
600
1000
600
1000
04
900
1500
900
1500
05
1200
2000
1200
2000
06
1500
2500
1500
2500
07
1800
3000
1800
3000
08
2250
3750
2250
3750
09
2550
4250
2550
4250
12
3000
5000
3000
5000
14
3750
6250
3750
6250
Air Quantity Limits (48PG03−14 Units)
UNIT
48PG
COOLING (cfm)
HEATING (cfm)
Min
Max
Min
Max
03
600
1000
600
1680
04 (Low Heat)
900
1500
600
1680
04 (Med Heat)
900
1500
940
2810
04 (High Heat)
900
1500
1130
2820
05 (Low Heat)
1200
2000
600
1680
05 (Med Heat)
1200
2000
940
2810
05 (High Heat)
1200
2000
1130
2820
06 (Low Heat)
1500
2500
940
2810
06 (Med Heat)
1500
2500
1130
2820
06 (High Heat)
1500
2500
1510
2520
07 (Low Heat)
1800
3000
940
2810
07 (Med Heat)
1800
3000
1130
2820
07 (High Heat)
1800
3000
1510
2520
08 (Low Heat)
2250
3750
2060
5160
08 (Med Heat)
2250
3750
2110
6870
08 (High Heat)
2250
3750
2450
4900
09 (Low Heat)
2550
4250
2060
5160
09 (Med Heat)
2550
4250
2110
6870
09 (High Heat)
2550
4250
2450
4900
12 (Low Heat)
3000
5000
2110
6870
12 (Med Heat)
3000
5000
2450
4900
12 (High Heat)
3000
5000
3150
6300
14 (Low Heat)
3750
6250
2110
6870
14 (Med Heat)
3750
6250
2450
4900
14 (High Heat)
3750
6250
3150
6300
Air Quantity Limits (48PM16−28 Units)
48PM
COOLING
GAS HEAT
HEATING
(NAT. GAS,
VERTICAL)
HEATING
(NAT. GAS,
HORIZONTAL)
HEATING
(PROPANE,
VERTICAL)
HEATING
(PROPANE,
HORIZONTAL)
Minimum
Cfm
Maximum
Cfm
Minimum Cfm
Minimum Cfm
Minimum Cfm
Minimum Cfm
16
4500
7500
High Heat (8 Cell)
5522
5522
5522
4920
Medium Heat (8 Cell)
4977
4977
4480
4480
Low Heat (5 Cell)
4218
4218
4218
3796
20
5400
9,000
High Heat (8 Cell)
5522
5522
5522
4920
Medium Heat (8 Cell)
4977
4977
4480
4480
Low Heat (5 Cell)
4218
4218
4218
3796
24
6000
10,000
High Heat (8 Cell)
5522
5522
5522
4920
Medium Heat (8 Cell)
4977
4977
4480
4480
Low Heat (5 Cell)
4218
4218
4218
3796
28
7500
12,000
High Heat (8 Cell)
5522
5470*
5522
4920*
Medium Heat (8 Cell)
4977
4977*
4480
4480*
Low Heat (5 Cell)
4218
4218
4218
3796
*7000 cfm minimum recommended above 1.0-in. wg external static pressure.
Air Quantity Limits (50PM16−28 Units)
50PM
COOLING
ELECTRIC HEAT
ELECTRIC HEAT
(Vertical)
ELECTRIC HEAT
(Horizontal)
Minimum Cfm
Maximum Cfm
Minimum Cfm
Minimum Cfm
16
4500
7500
High Heat (75 kW)
4,500
5,400
Medium Heat (50 kW)
3,750
4,800
Low Heat (25 kW)
3,750
3,750
20
5400
9,000
High Heat (75 kW)
4,500
5,400
Medium Heat (50 kW)
3,750
4,800
Low Heat (25 kW)
3,750
3,750
24
6000
10,000
High Heat (75 kW)
4,500
5,400
Medium Heat (50 kW)
3,750
4,800
Low Heat (25 kW)
3,750
3,750
28
7500
12,000
High Heat (75 kW)
4,500
5,400
Medium Heat (50 kW)
3,750
4,800
Low Heat (25 kW)
3,750
3,750
48/50PG and PM