APPENDIX D — ADDITIONAL START−UP DATA

Air Quantity Limits (50PG03−14 Units)

UNIT

50PG

COOLING (cfm)

HEATING (cfm)

OPTIONAL ELECTRIC HEAT

Min

Max

Min

Max

03

 600

1000

 600

1000

04

 900

1500

 900

1500

05

1200

2000

1200

2000

06

1500

2500

1500

2500

07

1800

3000

1800

3000

08

2250

3750

2250

3750

09

2550

4250

2550

4250

12

3000

5000

3000

5000

14

3750

6250

3750

6250

Air Quantity Limits (48PG03−14 Units)

UNIT

48PG

COOLING (cfm)

HEATING (cfm)

Min

Max

Min

Max

03

 600

1000

 600

1680

04 (Low Heat)

 900

1500

 600

1680

04 (Med Heat)

 900

1500

 940

2810

04 (High Heat)

 900

1500

1130

2820

05 (Low Heat)

1200

2000

 600

1680

05 (Med Heat)

1200

2000

 940

2810

05 (High Heat)

1200

2000

1130

2820

06 (Low Heat)

1500

2500

 940

2810

06 (Med Heat)

1500

2500

1130

2820

06 (High Heat)

1500

2500

1510

2520

07 (Low Heat)

1800

3000

 940

2810

07 (Med Heat)

1800

3000

1130

2820

07 (High Heat)

1800

3000

1510

2520

08 (Low Heat)

2250

3750

2060

5160

08 (Med Heat)

2250

3750

2110

6870

08 (High Heat)

2250

3750

2450

4900

09 (Low Heat)

2550

4250

2060

5160

09 (Med Heat)

2550

4250

2110

6870

09 (High Heat)

2550

4250

2450

4900

12 (Low Heat)

3000

5000

2110

6870

12 (Med Heat)

3000

5000

2450

4900

12 (High Heat)

3000

5000

3150

6300

14 (Low Heat)

3750

6250

2110

6870

14 (Med Heat)

3750

6250

2450

4900

14 (High Heat)

3750

6250

3150

6300

Air Quantity Limits (48PM16−28 Units)

48PM

COOLING

GAS HEAT

HEATING

(NAT. GAS,

VERTICAL)

HEATING

(NAT. GAS,

HORIZONTAL)

HEATING

(PROPANE,

VERTICAL)

HEATING

(PROPANE,

HORIZONTAL)

Minimum

Cfm

Maximum

Cfm

Minimum Cfm

Minimum Cfm

Minimum Cfm

Minimum Cfm

16

4500

7500

High Heat (8 Cell)

5522

5522

5522

4920

Medium Heat (8 Cell)

4977

4977

4480

4480

Low Heat (5 Cell)

4218

4218

4218

3796

20

5400

9,000

High Heat (8 Cell)

5522

5522

5522

4920

Medium Heat (8 Cell)

4977

4977

4480

4480

Low Heat (5 Cell)

4218

4218

4218

3796

24

6000

10,000

High Heat (8 Cell)

5522

5522

5522

4920

Medium Heat (8 Cell)

4977

4977

4480

4480

Low Heat (5 Cell)

4218

4218

4218

3796

28

7500

12,000

High Heat (8 Cell)

5522

5470*

5522

4920*

Medium Heat (8 Cell)

4977

4977*

4480

4480*

Low Heat (5 Cell)

4218

4218

4218

3796

*7000 cfm minimum recommended above 1.0-in. wg external static pressure.

Air Quantity Limits (50PM16−28 Units)

50PM

COOLING

ELECTRIC HEAT

ELECTRIC HEAT

(Vertical)

ELECTRIC HEAT

(Horizontal)

Minimum Cfm

Maximum Cfm

Minimum Cfm

Minimum Cfm

16

4500

 7500

High Heat (75 kW)

4,500

5,400

Medium Heat (50 kW)

3,750

4,800

Low Heat (25 kW)

3,750

3,750

20

5400

 9,000

High Heat (75 kW)

4,500

5,400

Medium Heat (50 kW)

3,750

4,800

Low Heat (25 kW)

3,750

3,750

24

6000

10,000

High Heat (75 kW)

4,500

5,400

Medium Heat (50 kW)

3,750

4,800

Low Heat (25 kW)

3,750

3,750

28

7500

12,000

High Heat (75 kW)

4,500

5,400

Medium Heat (50 kW)

3,750

4,800

Low Heat (25 kW)

3,750

3,750