Appendix a — local display and ccn tables (cont), Mode — operating modes (cont), Mode — alarms – Carrier 48/50PM C16-28 User Manual
Page 111

111
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — OPERATING MODES (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/
SUB-TABLE
CCN POINT
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
OAU (cont)
Outside Air Unit Diagnostic
OAU_DIAG
EX.FS
OAU Exhaust Fan Speed
xxx
%
OAUPESPD
A.EX
Actual Exhaust Air CFM
xxxxx
CFM
ACTEXCFM
C.EX
Command Exhaust Air CFM
xxxxx
CFM
CMDEXCFM
BP.SP
Building Pressure Setpnt
x.xx
in
H2O
OAU_BPSP
BP
Building Pressure
x.xx
in
H2O
OAU_BP
TM.LO
OA Tempring Lockout Temp
xx
°F
OATMPLOC
TM.SP
OA Tempring SAT Setpoint
xx
°F
OATMPSPT
OA.HT
OAU Tempering Heater
xxx
%
OAHEATER
ALM.1
OAU Motor Failure Alarm
Off/On
OAUALRM1
ALM.2
OAU Dirty Filter Alarm
Off/On
OAUALRM2
ALM.3
OA Low CFM Alarm
Off/On
OAUALRM3
ALM.4
OAU Alarm
Off/On
OAUALRM4
DMD.L
DEMAND LIMITING
DMDL
D.LMT
Demand Limit In Effect
No/Yes
MODEDMDL
LMT.C
Max Cool Stage In Effect
x
CSTGLIMT
LMT.H
Max Heat Stage In Effect
x
HSTGLIMT
REDL
Redline Activated
No/Yes
MODEREDL
SHED
Loadshed Activated
No/Yes
MODESHED
MAX.C
Max Allowed Cool Stages
x
MAXCSTGS
MAX.H
Max Allowed Heat Stages
x
MAXHSTGS
(Display TRIM see
Configuration)
Sensor Calibration
TRIM
Space Temp Calibration
30 to 130
°F
SPT_CAL
forcible
Space Temp Trim
30 to 30
^F
SPT_OFF
forcible
Supply Air Temp Calib.
30 to 130
°F
SAT_CAL
forcible
Supply Air Temp Trim
30 to 30
^F
SAT_OFF
forcible
Return Air Temp Calib.
30 to 130
°F
RAT_CAL
forcible
Return Air Temp Trim
30 to 30
^F
RAT_OFF
forcible
(LINKDATA = CCN
only)
CCN Linkage
LINKDATA
Supervisory Element #
xxx
SUPEADR
Supervisory Bus
xxx
SUPEBUS
Supervisory Block Number
xxx
BLOCKNUM
Average Occup. Heat Stp.
xxxx.x
°F
AOHS
Average Occup. Cool Stp.
xxxx.x
°F
AOCS
Average Unocc. Heat Stp.
xxxx.x
°F
AUHS
Average Unocc. Cool Stp.
xxxx.x
°F
AUCS
Average Zone Temperature
xxxx.x
°F
AZT
Average Occup. Zone Temp
xxxx.x
°F
AOZT
Linkage System Occupied?
No/Yes
LOCC
Next Occupied Day
"Mon",
"Tue", ... ,
"Sun"
3char
text
LNEXTOCD
Next Occupied Time
xx:xx
hh:mm
LNEXTOCC
forcible
Next Unoccupied Day
"Mon",
"Tue", ... ,
"Sun"
3char
text
LNEXTUOD
Next Unoccupied Time
xx:xx
hh:mm
LNEXTUNC
forcible
Last Unoccupied Day
"Mon",
"Tue", ... ,
"Sun"
3char text
LLASTUOD
Last Unoccupied Time
xx:xx
hh:mm
LLASTUNC
forcible
(OCCDEFM = CCN
only)
Occupancy Supervisory
OCCDEFM
Current Mode (1=Occup)
0,1
MODE
Current Occup Period #
0 to 8
PER_NO
TimeOverride in Effect
No/Yes
OVERLAST
TimeOverride Duration
0 to 4
hours
OVR_HRS
Current Occupied Tiime
xx.xx
hh:m
m
STRTTIME
Current Unoccupied Time
xx.xx
hh:mm
ENDTIME
Next Occupied Day
NXTOCDAY
Next Occupied Time
xx.xx
hh:mm
NXTOCTIM
Next Unoccupied Day
NXTUNDAY
Next Unoccupied Time
xx.xx
hh:mm
NXTUNTIM
Previous Unoccupied Day
PRVUNDAY
Previous Unoccupied Time
xx.xx
hh.mm
PRVUNTIM
MODE — ALARMS
ITEM
EXPANSION
RANGE
DEFAULT
CCN TABLE/
SUB-TABLE
CCN
POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
MAINTENANCE DISPLAY
ALARMS
ALARMS
R.CUR
Reset All Current Alarms
Yes/No
No
ALRESET
forcible
forcible
R.HIS
Reset Alarm History
Yes/No
No
ALHISCLR
forcible
forcible
CURR
Currently Active Alarms
alarm#
text string
ALARM01C -
ALARM25C
(repeat up to 25 alarms)
HIST
Alarm History
ALARM HISTORY
alarm#
alarm#-mm/dd/yy-
hh.mm-text string
(repeat up to 20 alarms)
48/50PG and PM