APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)

MODE — OPERATING MODES (cont)

ITEM

EXPANSION

RANGE

UNITS

CCN TABLE/
SUB-TABLE

CCN POINT

CCN WRITE

STATUS

DISPLAY

WRITE

STATUS

OAU (cont)

Outside Air Unit Diagnostic

OAU_DIAG

EX.FS

OAU Exhaust Fan Speed

xxx

%

OAUPESPD

A.EX

Actual Exhaust Air CFM

xxxxx

CFM

ACTEXCFM

C.EX

Command Exhaust Air CFM

xxxxx

CFM

CMDEXCFM

BP.SP

Building Pressure Setpnt

x.xx

in
H2O

OAU_BPSP

BP

Building Pressure

x.xx

in
H2O

OAU_BP

TM.LO

OA Tempring Lockout Temp

xx

°F

OATMPLOC

TM.SP

OA Tempring SAT Setpoint

xx

°F

OATMPSPT

OA.HT

OAU Tempering Heater

xxx

%

OAHEATER

ALM.1

OAU Motor Failure Alarm

Off/On

OAUALRM1

ALM.2

OAU Dirty Filter Alarm

Off/On

OAUALRM2

ALM.3

OA Low CFM Alarm

Off/On

OAUALRM3

ALM.4

OAU Alarm

Off/On

OAUALRM4

DMD.L

DEMAND LIMITING

DMDL

D.LMT

Demand Limit In Effect

No/Yes

MODEDMDL

LMT.C

Max Cool Stage In Effect

x

CSTGLIMT

LMT.H

Max Heat Stage In Effect

x

HSTGLIMT

REDL

Redline Activated

No/Yes

MODEREDL

SHED

Loadshed Activated

No/Yes

MODESHED

MAX.C

Max Allowed Cool Stages

x

MAXCSTGS

MAX.H

Max Allowed Heat Stages

x

MAXHSTGS

(Display TRIM ­ see

Configuration)

Sensor Calibration

TRIM

Space Temp Calibration

­30 to 130

°F

SPT_CAL

forcible

Space Temp Trim

­30 to 30

^F

SPT_OFF

forcible

Supply Air Temp Calib.

­30 to 130

°F

SAT_CAL

forcible

Supply Air Temp Trim

­30 to 30

^F

SAT_OFF

forcible

Return Air Temp Calib.

­30 to 130

°F

RAT_CAL

forcible

Return Air Temp Trim

­30 to 30

^F

RAT_OFF

forcible

(LINKDATA = CCN

only)

CCN ­ Linkage

LINKDATA

Supervisory Element #

xxx

SUPE­ADR

Supervisory Bus

xxx

SUPE­BUS

Supervisory Block Number

xxx

BLOCKNUM

Average Occup. Heat Stp.

xxxx.x

°F

AOHS

Average Occup. Cool Stp.

xxxx.x

°F

AOCS

Average Unocc. Heat Stp.

xxxx.x

°F

AUHS

Average Unocc. Cool Stp.

xxxx.x

°F

AUCS

Average Zone Temperature

xxxx.x

°F

AZT

Average Occup. Zone Temp

xxxx.x

°F

AOZT

Linkage System Occupied?

No/Yes

LOCC

Next Occupied Day

"Mon",
"Tue", ... ,
"Sun"

3­char
text

LNEXTOCD

Next Occupied Time

xx:xx

hh:mm

LNEXTOCC

forcible

Next Unoccupied Day

"Mon",
"Tue", ... ,
"Sun"

3­char
text

LNEXTUOD

Next Unoccupied Time

xx:xx

hh:mm

LNEXTUNC

forcible

Last Unoccupied Day

"Mon",
"Tue", ... ,
"Sun"

3­char text

LLASTUOD

Last Unoccupied Time

xx:xx

hh:mm

LLASTUNC

forcible

(OCCDEFM = CCN

only)

Occupancy Supervisory

OCCDEFM

Current Mode (1=Occup)

0,1

MODE

Current Occup Period #

0 to 8

PER_NO

Time­Override in Effect

No/Yes

OVERLAST

Time­Override Duration

0 to 4

hours

OVR_HRS

Current Occupied Tiime

xx.xx

hh:m
m

STRTTIME

Current Unoccupied Time

xx.xx

hh:mm

ENDTIME

Next Occupied Day

NXTOCDAY

Next Occupied Time

xx.xx

hh:mm

NXTOCTIM

Next Unoccupied Day

NXTUNDAY

Next Unoccupied Time

xx.xx

hh:mm

NXTUNTIM

Previous Unoccupied Day

PRVUNDAY

Previous Unoccupied Time

xx.xx

hh.mm

PRVUNTIM

MODE — ALARMS

ITEM

EXPANSION

RANGE

DEFAULT

CCN TABLE/
SUB-TABLE

CCN

POINT

CCN

WRITE

STATUS

DISPLAY

WRITE

STATUS

MAINTENANCE DISPLAY

ALARMS

ALARMS

R.CUR

Reset All Current Alarms

Yes/No

No

ALRESET

forcible

forcible

R.HIS

Reset Alarm History

Yes/No

No

ALHISCLR

forcible

forcible

CURR

Currently Active Alarms

alarm#

text string

ALARM01C -
ALARM25C

(repeat up to 25 alarms)

HIST

Alarm History

ALARM HISTORY

alarm#

alarm#-mm/dd/yy-
hh.mm-text string

(repeat up to 20 alarms)