beautypg.com

Fan performance — 48pgd06 vertical units – Carrier 48/50PM C16-28 User Manual

Page 116

background image

116

Fan Performance — 48PGF05 Vertical Units

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1200

520

0.17

628

0.24

723

0.33

811

0.41

 892

0.51

1300

545

0.20

648

0.28

739

0.37

823

0.46

 902

0.56

1400

570

0.24

668

0.32

756

0.41

837

0.51

 913

0.61

1500

596

0.28

691

0.37

775

0.46

853

0.56

 927

0.67

1600

623

0.32

714

0.42

795

0.52

870

0.62

 942

0.73

1700

650

0.37

737

0.48

816

0.58

889

0.69

 958

0.80

1800

677

0.43

762

0.54

838

0.65

909

0.76

 976

0.88

1900

705

0.50

787

0.61

861

0.72

929

0.84

 994

0.97

2000

734

0.57

813

0.68

884

0.80

951

0.93

1014

1.06

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1200

 968

0.61

1040

0.71

1108

0.82

1172

0.93

1233

1.04

1300

 976

0.66

1046

0.77

1112

0.88

1176

1.00

1237

1.11

1400

 985

0.72

1054

0.83

1119

0.95

1181

1.07

1241

1.19

1500

 996

0.78

1063

0.90

1127

1.02

1188

1.14

1247

1.27

1600

1009

0.85

1074

0.97

1136

1.09

1196

1.22

1254

1.35

1700

1024

0.92

1087

1.05

1147

1.17

1205

1.31

1262

1.44

1800

1039

1.00

1100

1.13

1159

1.26

1216

1.40

1272

1.54

1900

1056

1.09

1116

1.22

1173

1.36

1229

1.50

1283

1.64

2000

1074

1.19

1132

1.32

1188

1.46

1242

1.61

1295

1.75

LEGEND
Bhp -
Brake Horsepower

High Range Motor/Drive Required

NOTES:

1. Motor drive range is 596 to 910 rpm for low range motor/drive and 828 to 1173 rpm
for high range motor/drive. All other rpms require a field‐supplied drive.
2. Maximum continuous bhp is 0.85 for low range motor/drive and 1.60 (single phase)
and 2.40 (3 phase) for high range motor/drive.
3. See General Fan Performance Notes.

Fan Performance — 48PGD06 Vertical Units

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1500

593

0.27

688

0.37

 773

0.46

 851

0.56

 925

0.67

1600

620

0.32

711

0.42

 793

0.52

 868

0.62

 939

0.73

1700

646

0.37

734

0.47

 813

0.58

 886

0.69

 955

0.80

1800

673

0.43

758

0.53

 835

0.64

 905

0.76

 972

0.88

1900

700

0.49

783

0.60

 857

0.72

 925

0.84

 990

0.96

2000

728

0.56

807

0.68

 879

0.80

 946

0.92

1009

1.05

2100

755

0.63

833

0.76

 903

0.88

 968

1.01

1029

1.14

2200

783

0.71

858

0.84

 926

0.97

 990

1.11

1050

1.24

2300

811

0.80

884

0.94

 950

1.07

1012

1.21

1071

1.35

2400

840

0.90

910

1.04

 975

1.18

1035

1.33

1092

1.47

2500

868

1.00

937

1.15

1000

1.30

1059

1.45

1115

1.60

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1500

 995

0.78

1061

0.89

1125

1.01

1186

1.14

1245

1.26

1600

1007

0.85

1072

0.96

1134

1.09

1194

1.22

1252

1.35

1700

1021

0.92

1084

1.04

1145

1.17

1203

1.30

1260

1.44

1800

1036

1.00

1098

1.13

1157

1.26

1214

1.39

1269

1.53

1900

1053

1.08

1112

1.22

1170

1.35

1226

1.49

1280

1.63

2000

1070

1.18

1128

1.31

1184

1.45

1238

1.60

1291

1.74

2100

1088

1.28

1145

1.42

1199

1.56

1253

1.71

1304

1.86

2200

1107

1.38

1162

1.53

1216

1.68

1268

1.83

1318

1.98

2300

1127

1.50

1181

1.65

1233

1.80

1284

1.95

1333

2.11

2400

1147

1.62

1200

1.77

1251

1.93

1300

2.09

1349

2.25

2500

1168

1.75

1220

1.91

1270

2.07

1318

2.23

1365

2.40

LEGEND
Bhp -
Brake Horsepower

High Range Motor/Drive Required

NOTES:

1. Motor drive range is 690 to 978 rpm for low range motor/drive and 929 to 1261 rpm
for high range motor/drive. All other rpms require a field‐supplied drive.
2. Maximum continuous bhp is 0.85 (single phase) and 2.40 (3 phase) for low range
motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive.
3. See General Fan Performance Notes.

48/50PG and PM