112
APPENDIX B — CONTROL MODES WITH
Humidi−MiZer
SYSTEM AND ECONOMIZER
Thermostat input shown for cooling demand (versus temperature
sensor and set point). Humidistat input shown for
dehumidification demand (versus relative humidity sensor and set
point). Economizer cooling availability is dependent on outdoor
temperature or enthalpy.
Circuit Subcooling mode = REHEAT 1
Circuit HGRH mode = hot gas reheat = REHEAT 2
Circuit ON mode = normal cooling
Thermostat Control type configuration = 0 = Adaptive, or Unit
Control Type configuration = 3 = Space Temperature, for
Dual-circuit and Tri-Circuit units results in added staging timers
and flex between 1-stage Y1 and 2-stage Y1.
SINGLE-CIRCUIT UNITS
(Thermostat Control Type configuration is ignored)
ECONO AVAILABLE?
Y1
Y2
HUMIDISTAT
CIRCUIT A
ECONOMIZER
NO
OFF
OFF
LOW
OFF
Min. Position
(Econo closed if fan off)
NO
OFF
OFF
HIGH
HGRH
Min. Position
NO
ON
OFF
HIGH
Subcooling
Min. Position
NO
OFF
ON
HIGH
Subcooling
Min. Position
alarm T411: Y2 without Y1
NO
ON
ON
HIGH
Subcooling
Min. Position
no alarm
NO
ON
OFF
LOW
ON
Min. Position
NO
OFF
ON
LOW
ON
Min. Position
alarm T411: Y2 without Y1
NO
ON
ON
LOW
ON
Min. Position
no alarm
YES
OFF
OFF
LOW
OFF
Min. Position
(Econo closed if fan off)
YES
OFF
OFF
HIGH
HGRH
Min. Position
YES
ON
OFF
HIGH
Subcooling
Min. Position
YES
OFF
ON
HIGH
Subcooling
Min. Position
alarm T411: Y2 without Y1
YES
ON
ON
HIGH
Subcooling
Min. Position
no alarm
YES
ON
OFF
LOW
OFF or ON
Cooling
YES
OFF
ON
LOW
OFF or ON
Cooling
alarm T411: Y2 without Y1
YES
ON
ON
LOW
OFF or ON
Cooling
no alarm
DUAL CIRCUIT UNITS
1-Stage Y1 (Thermostat Control Type configuration = 1)
and 2-Stage Y1 (Thermostat Control Type configuration = 2)
ECONO AVAILABLE?
Y1
Y2
HUMIDISTAT
CIRCUIT A
CIRCUIT B
ECONOMIZER
NO
OFF
OFF
LOW
OFF
OFF
Min. Position
(Econo closed if fan off)
NO
OFF
OFF
HIGH
HGRH
HGRH
Min. Position
NO
ON
OFF
HIGH
Subcooling
HGRH
Min. Position
NO
OFF
ON
HIGH
Subcooling
Subcooling
Min. Position
alarm T411: Y2 without Y1
NO
ON
ON
HIGH
Subcooling
Subcooling
Min. Position
NO
ON
OFF
LOW
ON
OFF
Min. Position
NO
OFF
ON
LOW
ON
ON
Min. Position
alarm T411: Y2 without Y1
NO
ON
ON
LOW
ON
ON
Min. Position
YES
OFF
OFF
LOW
OFF
OFF
Min. Position
(Econo closed if fan off)
YES
OFF
OFF
HIGH
HGRH
HGRH
Min. Position
YES
ON
OFF
HIGH
Subcooling
HGRH
Min. Position
YES
OFF
ON
HIGH
Subcooling
Subcooling
Min. Position
alarm T411: Y2 without Y1
YES
ON
ON
HIGH
Subcooling
Subcooling
Min. Position
YES
ON
OFF
LOW
OFF or ON
OFF
Cooling
YES
OFF
ON
LOW
OFF or ON
OFF or ON
Cooling
alarm T411: Y2 without Y1
YES
ON
ON
LOW
OFF or ON
OFF or ON
Cooling
DUAL-CIRCUIT UNITS
Digital (Thermostat Control Type configuration = 3)
ECONO AVAILABLE?
Y1
Y2
HUMIDISTAT
CIRCUIT A
CIRCUIT B
ECONOMIZER
NO
OFF
OFF
LOW
OFF
OFF
Min. Position
(Econo closed if fan off)
NO
OFF
OFF
HIGH
HGRH
OFF
Min. Position
NO
ON
OFF
HIGH
HGRH
HGRH
Min. Position
NO
OFF
ON
HIGH
Subcooling
HGRH
Min. Position
NO
ON
ON
HIGH
Subcooling
Subcooling
Min. Position
NO
ON
OFF
LOW
ON
OFF
Min. Position
NO
OFF
ON
LOW
ON
ON
Min. Position
NO
ON
ON
LOW
ON
ON
Min. Position
YES
OFF
OFF
LOW
OFF
OFF
Min. Position
(Econo closed if fan off)
YES
OFF
OFF
HIGH
HGRH
OFF
Min. Position
YES
ON
OFF
HIGH
HGRH
HGRH
Min. Position
YES
OFF
ON
HIGH
Subcooling
HGRH
Min. Position
YES
ON
ON
HIGH
Subcooling
Subcooling
Min. Position
YES
ON
OFF
LOW
OFF or ON
OFF
Cooling
YES
OFF
ON
LOW
OFF or ON
OFF or ON
Cooling
YES
ON
ON
LOW
OFF or ON
OFF or ON
Cooling
48/50PG and PM