APPENDIX B — CONTROL MODES WITH

Humidi−MiZer

SYSTEM AND ECONOMIZER

Thermostat input shown for cooling demand (versus temperature
sensor and set point). Humidistat input shown for
dehumidification demand (versus relative humidity sensor and set
point). Economizer cooling availability is dependent on outdoor
temperature or enthalpy.

Circuit Subcooling mode = REHEAT 1

Circuit HGRH mode = hot gas reheat = REHEAT 2

Circuit ON mode = normal cooling

Thermostat Control type configuration = 0 = Adaptive, or Unit
Control Type configuration = 3 = Space Temperature, for
Dual-circuit and Tri-Circuit units results in added staging timers
and flex between 1-stage Y1 and 2-stage Y1.

SINGLE-CIRCUIT UNITS

(Thermostat Control Type configuration is ignored)

ECONO AVAILABLE?

Y1

Y2

HUMIDISTAT

CIRCUIT A

ECONOMIZER

NO

OFF

OFF

LOW

OFF

Min. Position

(Econo closed if fan off)

NO

OFF

OFF

HIGH

HGRH

Min. Position

NO

ON

OFF

HIGH

Subcooling

Min. Position

NO

OFF

ON

HIGH

Subcooling

Min. Position

alarm T411: Y2 without Y1

NO

ON

ON

HIGH

Subcooling

Min. Position

no alarm

NO

ON

OFF

LOW

ON

Min. Position

NO

OFF

ON

LOW

ON

Min. Position

alarm T411: Y2 without Y1

NO

ON

ON

LOW

ON

Min. Position

no alarm

YES

OFF

OFF

LOW

OFF

Min. Position

(Econo closed if fan off)

YES

OFF

OFF

HIGH

HGRH

Min. Position

YES

ON

OFF

HIGH

Subcooling

Min. Position

YES

OFF

ON

HIGH

Subcooling

Min. Position

alarm T411: Y2 without Y1

YES

ON

ON

HIGH

Subcooling

Min. Position

no alarm

YES

ON

OFF

LOW

OFF or ON

Cooling

YES

OFF

ON

LOW

OFF or ON

Cooling

alarm T411: Y2 without Y1

YES

ON

ON

LOW

OFF or ON

Cooling

no alarm

DUAL CIRCUIT UNITS

1-Stage Y1 (Thermostat Control Type configuration = 1)

and 2-Stage Y1 (Thermostat Control Type configuration = 2)

ECONO AVAILABLE?

Y1

Y2

HUMIDISTAT

CIRCUIT A

CIRCUIT B

ECONOMIZER

NO

OFF

OFF

LOW

OFF

OFF

Min. Position

(Econo closed if fan off)

NO

OFF

OFF

HIGH

HGRH

HGRH

Min. Position

NO

ON

OFF

HIGH

Subcooling

HGRH

Min. Position

NO

OFF

ON

HIGH

Subcooling

Subcooling

Min. Position

alarm T411: Y2 without Y1

NO

ON

ON

HIGH

Subcooling

Subcooling

Min. Position

NO

ON

OFF

LOW

ON

OFF

Min. Position

NO

OFF

ON

LOW

ON

ON

Min. Position

alarm T411: Y2 without Y1

NO

ON

ON

LOW

ON

ON

Min. Position

YES

OFF

OFF

LOW

OFF

OFF

Min. Position

(Econo closed if fan off)

YES

OFF

OFF

HIGH

HGRH

HGRH

Min. Position

YES

ON

OFF

HIGH

Subcooling

HGRH

Min. Position

YES

OFF

ON

HIGH

Subcooling

Subcooling

Min. Position

alarm T411: Y2 without Y1

YES

ON

ON

HIGH

Subcooling

Subcooling

Min. Position

YES

ON

OFF

LOW

OFF or ON

OFF

Cooling

YES

OFF

ON

LOW

OFF or ON

OFF or ON

Cooling

alarm T411: Y2 without Y1

YES

ON

ON

LOW

OFF or ON

OFF or ON

Cooling

DUAL-CIRCUIT UNITS

Digital (Thermostat Control Type configuration = 3)

ECONO AVAILABLE?

Y1

Y2

HUMIDISTAT

CIRCUIT A

CIRCUIT B

ECONOMIZER

NO

OFF

OFF

LOW

OFF

OFF

Min. Position

(Econo closed if fan off)

NO

OFF

OFF

HIGH

HGRH

OFF

Min. Position

NO

ON

OFF

HIGH

HGRH

HGRH

Min. Position

NO

OFF

ON

HIGH

Subcooling

HGRH

Min. Position

NO

ON

ON

HIGH

Subcooling

Subcooling

Min. Position

NO

ON

OFF

LOW

ON

OFF

Min. Position

NO

OFF

ON

LOW

ON

ON

Min. Position

NO

ON

ON

LOW

ON

ON

Min. Position

YES

OFF

OFF

LOW

OFF

OFF

Min. Position

(Econo closed if fan off)

YES

OFF

OFF

HIGH

HGRH

OFF

Min. Position

YES

ON

OFF

HIGH

HGRH

HGRH

Min. Position

YES

OFF

ON

HIGH

Subcooling

HGRH

Min. Position

YES

ON

ON

HIGH

Subcooling

Subcooling

Min. Position

YES

ON

OFF

LOW

OFF or ON

OFF

Cooling

YES

OFF

ON

LOW

OFF or ON

OFF or ON

Cooling

YES

ON

ON

LOW

OFF or ON

OFF or ON

Cooling

48/50PG and PM