Carrier 48/50PM C16-28 User Manual
Page 173
![background image](/manuals/64998/173/background.png)
173
Evaporator Fan Motor Specifications − 48PM16−28 (cont)
UNIT
48PM
DRIVE
ORIENTATION
VOLTAGE
EFFICIENCY %
MAX BHP
MAX AMPS
24
Low
Vertical
208
85.8
4.26
10.6
230
85.8
4.26
9.6
460
85.8
4.26
4.8
575
87.5
5.75
6.0
Mid-Low
Vertical
208
87.5
5.37
15.8
230
87.5
5.75
15.4
460
87.5
5.75
7.7
575
87.5
5.75
6.0
Mid-High
Vertical
208
88.5
7.66
22.0
230
88.5
8.51
22.0
460
88.5
8.63
11.6
575
88.5
8.63
9.4
High
Vertical
208
89.5
9.94
28.0
230
89.5
10.45
28.0
460
89.5
11.19
15.0
575
89.5
11.50
12.0
Low
Horizontal
208
N/A
N/A
N/A
230
N/A
N/A
N/A
460
N/A
N/A
N/A
575
N/A
N/A
N/A
Mid-Low
Horizontal
208
85.8
4.26
10.6
230
85.8
4.26
9.6
460
85.8
4.26
4.8
575
87.5
5.75
6.0
Mid-High
Horizontal
208
87.5
5.37
15.8
230
87.5
5.75
15.4
460
87.5
5.75
7.7
575
87.5
5.75
6.0
High
Horizontal
208
88.5
7.66
22.0
230
88.5
8.51
22.0
460
88.5
8.63
11.6
575
88.5
8.63
9.4
28
Low
Vertical
208
87.5
5.37
15.8
230
87.5
5.75
15.4
460
87.5
5.75
7.7
575
87.5
5.75
6.0
Mid-Low
Vertical
208
87.5
5.37
15.8
230
87.5
5.75
15.4
460
87.5
5.75
7.7
575
87.5
5.75
6.0
Mid-High
Vertical
208
88.5
7.66
22.0
230
88.5
8.51
22.0
460
88.5
8.63
11.6
575
88.5
8.63
9.4
High
Vertical
208
89.5
9.94
28.0
230
89.5
10.45
28.0
460
89.5
11.19
15.0
575
89.5
11.50
12.0
Low
Horizontal
208
87.5
5.37
15.8
230
87.5
5.75
15.4
460
87.5
5.75
7.7
575
87.5
5.75
6.0
Mid-Low
Horizontal
208
87.5
5.37
15.8
230
87.5
5.75
15.4
460
87.5
5.75
7.7
575
87.5
5.75
6.0
Mid-High
Horizontal
208
88.5
7.66
22.0
230
88.5
8.51
22.0
460
88.5
8.63
11.6
575
88.5
8.63
9.4
High
Horizontal
208
89.5
9.94
28.0
230
89.5
10.45
28.0
460
89.5
11.19
15.0
575
89.5
11.50
12.0
NOTES:
1. Extensive motor and electrical testing ensures that the motors can be utilized with confidence up to the maximum applied bhp, watts, and amps. Using the fan
motor up to the maximum ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
2. All Indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October
24, 1997.