beautypg.com

Fan performance − 48pgf06 vertical units – Carrier 48/50PM C16-28 User Manual

Page 117

background image

117

Fan Performance — 48PGE06 Vertical Units

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1500

607

0.29

700

0.38

 784

0.47

 861

0.57

 934

0.68

1600

634

0.33

724

0.43

 804

0.53

 879

0.64

 950

0.75

1700

662

0.39

748

0.49

 826

0.60

 898

0.71

 967

0.82

1800

690

0.45

773

0.55

 848

0.67

 918

0.78

 985

0.90

1900

719

0.51

799

0.63

 872

0.74

 940

0.86

1004

0.98

2000

748

0.59

825

0.70

 896

0.83

 962

0.95

1024

1.08

2100

777

0.67

852

0.79

 920

0.92

 985

1.05

1045

1.18

2200

807

0.75

879

0.88

 946

1.01

1008

1.15

1067

1.29

2300

837

0.85

907

0.98

 971

1.12

1032

1.26

1090

1.40

2400

867

0.95

935

1.09

 998

1.24

1057

1.38

1113

1.53

2500

897

1.06

963

1.21

1024

1.36

1082

1.51

1137

1.66

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1500

1004

0.79

1070

0.91

1133

1.03

1194

1.15

1253

1.28

1600

1017

0.86

1081

0.98

1143

1.11

1203

1.24

1260

1.37

1700

1032

0.94

1094

1.06

1155

1.19

1213

1.32

1269

1.46

1800

1048

1.02

1109

1.15

1168

1.28

1224

1.42

1279

1.56

1900

1066

1.11

1125

1.24

1182

1.38

1237

1.52

1291

1.66

2000

1084

1.21

1142

1.35

1197

1.49

1251

1.63

1304

1.78

2100

1104

1.31

1160

1.45

1214

1.60

1267

1.75

1318

1.90

2200

1124

1.43

1179

1.57

1231

1.72

1283

1.87

1333

2.03

2300

1145

1.55

1198

1.70

1250

1.85

1300

2.01

1349

2.17

2400

1167

1.68

1219

1.83

1269

1.99

1318

2.15

1366

2.31

2500

1189

1.82

1240

1.97

1290

2.14

1337

2.30

LEGEND
Bhp -
Brake Horsepower

NOTES:

1. Motor drive range is 690 to 978 rpm for low range motor/drive and 929 to 1261 rpm
for high range motor/drive. All other rpms require a field‐supplied drive.
2. Maximum continuous bhp is 0.85 (single phase) and 2.40 (3 phase) for low range
motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive.
3. See General Fan Performance Notes.

Fan Performance − 48PGF06 Vertical Units

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1500

620

0.30

711

0.39

 794

0.49

 871

0.59

 944

0.70

1600

648

0.35

736

0.45

 816

0.55

 890

0.65

 960

0.76

1700

677

0.40

762

0.51

 838

0.61

 910

0.72

 978

0.84

1800

707

0.47

788

0.58

 862

0.69

 931

0.80

 997

0.92

1900

737

0.54

815

0.65

 887

0.77

 954

0.89

1017

1.01

2000

767

0.61

843

0.73

 912

0.85

 977

0.98

1039

1.11

2100

798

0.70

871

0.82

 938

0.95

1001

1.08

1061

1.21

2200

829

0.79

900

0.92

 965

1.05

1026

1.19

1084

1.33

2300

861

0.89

929

1.03

 992

1.17

1052

1.31

1108

1.45

2400

893

1.00

959

1.15

1020

1.29

1078

1.43

1133

1.58

2500

925

1.12

989

1.27

1048

1.42

1105

1.57

1158

1.72

AIRFLOW

(CFM)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1500

1013

0.81

1078

0.92

1141

1.05

1202

1.17

1260

1.30

1600

1027

0.88

1091

1.00

1152

1.13

1211

1.25

1269

1.39

1700

1043

0.96

1105

1.08

1165

1.21

1222

1.35

1278

1.48

1800

1060

1.05

1120

1.18

1179

1.31

1235

1.44

1290

1.59

1900

1078

1.14

1137

1.27

1194

1.41

1249

1.55

1302

1.70

2000

1098

1.24

1155

1.38

1210

1.52

1264

1.67

1316

1.81

2100

1119

1.35

1174

1.49

1228

1.64

1280

1.79

1331

1.94

2200

1140

1.47

1195

1.62

1247

1.77

1298

1.92

1348

2.08

2300

1163

1.60

1216

1.75

1267

1.90

1317

2.06

1365

2.22

2400

1186

1.73

1238

1.89

1288

2.05

1336

2.21

1384

2.37

2500

1210

1.88

1261

2.04

1309

2.20

1357

2.37

LEGEND
Bhp -
Brake Horsepower

NOTES:

1. Motor drive range is 690 to 978 rpm for low range motor/drive and 929 to 1261 rpm
for high range motor/drive. All other rpms require a field‐supplied drive.
2. Maximum continuous bhp is 0.85 (single phase) and 2.40 (3 phase) for low range
motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive.
3. See General Fan Performance Notes.

48/50PG and PM