Advanced Menu

ADVANCED

APPLICATION

CB PROGRAMS
COMMUNICATION
DATE/TIME
DEVICE
INPUTS
LIMITS

The Advanced Menu displays various submenus.

Not all submenus can be seen on the screen at one

time. Scroll up or down to see additional submenus.
NOTE: The Advanced Menu has more submenus

than can appear on the screen at once. Keep

scrolling up or down to see all the options.

(Advanced) Application and Additional Setup

APPLICATION
DEGREES SCALE: °F

APP:

OPT: 4-PIPE
ADDITIONAL SETUP

FAN COIL

ADDITIONAL SETUP

DAMPER

FAN
HUMIDITY
MOTION SENSOR
OPTIMUM START
SENSORS
STAGING

Be sure to select the correct default °F/°C

temperature scale FIRST! To change the

temperature scale after the application is

configured, the selected application will need to be

reset to Not Configured. The change will also not

affect the display until after the FlexStat has been

restarted.
NOTE: During normal operation (after

configuration), the °F/°C temperature scale

can be toggled on the display by pressing

and holding the Enter button. See

Display

Options on page 5

.

The type of application (as well as the model of

FlexStat) affects the context-sensitive options under

Additional Setup.
NOTE: If a FlexStat is configured and then a

different application is desired (e.g., AHU

instead of FCU), restoring the FlexStat

to its factory defaults first and then

reconfiguring it is highly recommended.

See

Restore Factory on page 27

.

Auxiliary Heat (Heat Pump Only) Setup

AUX HEAT SETUP

AUX HEAT:

DELAY (MINS): 60
COMP OAT LOW: 40° F

COMP LOCKOUT

For HPUs, auxiliary heat can be set for none, with

compressor lockout, or without compressor lockout.
The Delay time controls how long the space temper-

ature must be below the auxiliary heat’s start tem-

perature before auxiliary heat will turn on. (For more

details, see the Auxiliary/Emergency Heat section

under Sequence of Operation (BAC-1xx63/1xxx63) in

the

FlexStat Application Guide

.)

Comp OAT Low (AV17) is the outside air tempera-

ture value, below which the compressor is locked out

(when lockout is enabled). The user interface min./

max. limits are 0 and 70 degrees, with a default value

of 40 degrees F.

Damper Setup

DAMPER SETUP

ECON:

DCV: ADVANCED
DCV SETUP
MIN POSITION: 0%
CNTRL (0–100%): 2–10 V
ECON ENBLE TEMP: 55° F
LOW LIMIT ALARM: 45° F

MODULATING

If the Economizer option is selected when there is

no mixed air temperature sensor connected, a Low

Limit Alarm will result. See

Alarms on page 23

. A Low

Limit Alarm will close the dampers, open the hot

water valve if present, and shut the unit down.
Outside Air Damper Low Limit maintains a mini-

mum mixed air temperature. It will override econo-

mizing, DCV, or other calls for ventilation if low

temperature threatens to damage equipment. For

modulating economizers, OAD Low Limit is enabled

by default but can be disabled if desired (such as for

an AHU with gas heat).

CAUTION

Do not disable the OAD Low Limit if coils or
other equipment may consequently be damaged
by low temperatures.