FlexStat 14

Operation Guide, Rev. R

finished and returned the ventilation

rate to “normal” operation).

Pre-purge—If enabled in the

programming (disabled by default),

the space is ventilated with maximum

outside air for 60 minutes before the

occupied start time. (See Startup.)

Startup—If pre-purge is disabled

(default) and the motion sensor

detects motion during the 20 minutes

after occupied start time, the space is

ventilated with maximum outside air

until 20 minutes after occupied start

time.

Standby—After the motion sensor has

not detected motion for 30 minutes,

temperature setpoints are adjusted

(down for heating and up for cooling),

and the outside air damper is closed.

Recovery—After a period in which

the supply fan was off, the space is

ventilated with an increased percentage

of outside air (to compensate for the

previous reduced ventilation).

Override—Ventilation override has

been manually selected from the DCV

menu, and the space is temporarily

(30 minutes default) driven to the full

ventilation position (for maximum

design occupancy) if it is not already

at that position. See

DCV (Demand

Control Ventilation) on page 24

.

VENT OVRIDE (MINS) = Amount of time for

Ventilation Override operation (30 minutes

default). See

DCV (Demand Control

Ventilation) on page 24

.

(Advanced) Communications (BACnet)

COMMUNICATIONS

ACTIVE:

STATUS: ACTIVE
ETHERNET SETTINGS
IP SETTINGS
FOREIGN DEV SETTINGS
MS/TP SETTINGS

CONFIGURE

COMMUNICATIONS

ACTIVE:

STATUS: ACTIVE
MAC: 00:D0:6F:89:00:01

ETHERNET

COMMUNICATIONS

ACTIVE:

STATUS: ACTIVE
IP ADDRESS: 192.168.1.254
SUBNET MASK: 255.255.0.0
GATEWAY: 255.255.255.255
UDP PORT: 47808

IP

COMMUNICATIONS

ACTIVE:

STATUS: ACTIVE
IP ADDRESS: 172.16.1.254
UDP PORT: 47808
TIME TO LIVE (SECS): 600

FOREIGN DEVICE

COMMUNICATIONS

ACTIVE:

STATUS: ACTIVE
MAC ADDRESS: 1
BAUD: 38400
AUTO-BAUD: OFF
MAX MASTER: 127

MS/TP

For MS/TP communications, connect the EIA-485

wiring to –A and +B terminals on the backplate (see

the relevant model’s installation guide). For Ethernet

IP, and Foreign Device communications (on relevant

“E” models), plug an Ethernet cable directly into the

RJ-45 modular jack on the back of the FlexStat.
To set protocol and parameters for BACnet

communications,
1. Select Active: Configure.
2. Configure the desired protocol.
3. Select Active: [protocol] and restart the FlexStat.
NOTE: Even if MS/TP is the only option in

firmware R2.0.0.6 and later, ACTIVE:

CONFIGURE MUST FIRST BE

SELECTED before any of the values can

be changed! Otherwise the values are read

only.

Only one protocol can be enabled at any time. The

IP/Ethernet modes do not serve as routers for the

MS/TP connection.
To communicate with a KMD-5576 through the data

port at the bottom of the case, IP/Ethernet-enabled

FlexStat models in one of the Ethernet or IP modes

must (temporarily) be set for MS/TP mode (and

restarted)!