FlexStat 17

Operation Guide, Rev. R

(Advanced) BACnet Device Properties

DEVICE

INSTANCE:

NAME: FlexStat_101
LOCATION: KMC Controls

1

To set the BACnet device instance, name, and

location, press:
1. Up

/Down to move among entries.

2. Enter to select.
NOTE: In firmware versions R1.3.0.4 and earlier,

the FlexStat could also be restarted or

restored to factory defaults from this

menu. In R2.0.x, this function was moved to

a separate menu. See

(Advanced) Restart/

Restore on page 18

and

Resetting the FlexStat

on page 26

for more information about that

function.

(Advanced) Inputs

INPUTS
1: SPACE TEMP

2:

3: MIXED AIR TEMP
4: OUTSIDE AIR TEMP
5: SPACE HUMIDITY
7: REMOTE SPACE TEMP
8: AI_08

DISCH AIR TEMP

INPUT #2

DISCH AIR TEMP
VALUE: 60.0° F
CAL. OFFSET: 0.0
OUT-OF-SERVICE: FALSE
FILTER WEIGHT: 6

SENSOR:

10K TYPE III

Inputs vary according to model, selected application,

and selected application options. See

(Advanced) Ap-

plication and Additional Setup on page 7

.

Value will show a temperature reading or a voltage

(0.0 to 3.0), depending on the sensor. Analog sensors

(built-in or external) can be calibrated by adjusting

the Calibration Offset value (see the

FlexStat Appli-

cation Guide

for details).

Filter Weight smooths (dampens) input value read-

ings, reducing sensitivity to noise and temperature

spikes. Smaller filter weight values (more sensitive)

cause the sensor readings to react more quickly to

sudden changes, and larger values (more stable)

cause sensor readings to react more slowly to sudden

changes. Areas subject to sudden swings of tempera-

ture from factors such as door openings and closings

may benefit from adjusting the filter weight. Tempo-

rarily reducing filter weight may also be helpful for

some diagnostic or commissioning purposes (but the

defaults should be restored for normal operation).

For much more information, see the

FlexStat Appli-

cation Guide

.

Calibration Offset can be used to calibrate an analog

input by changing the value. For details of calibrat-

ing the internal temperature sensor, see the

FlexStat

Application Guide

. (A CO

2

sensor has a different

calibration method, using a gas cylinder—see the

FlexStat Application Guide

.)

Out-of-Service: False” means the input is active (not

out of service). If it is “true,” the input is inactive.

The FlexStat menu only shows the status. The status

can only be changed through BACstage or TotalCon-

trol.

(Advanced) Temp. Setpoint Limits

LIMITS

OCC MIN CLG:

OCC MAX HTG: 80° F
UNOCC MIN CLG: 66° F
UNOCC MAX HTG: 80° F
MIN SETPT DIFF: 2° F

66° F

This menu permits changes to the minimum and

maximum allowed user/operator setpoint values.
NOTE: For

Minimum Setpoint Differential, see the

diagram.

(

Colder

Room Temperature

Warmer

)

Deadband

Cooling

Setpoint

Heating

Setpoint

Setpoint

Span

Min. Setpoint

Differential

Deadband

Other

Common

Terms

R1.4.0.1 and

Earlier Firmware

R2.0.0.x and

Later Firmware

Throttling

Range

Deadband

Setpoint

Span

Throttling

Range

Heating

Proportional

Band

Cooling

Proportional

Band

Minimum

Setpoint

Differential