Page 17: Type ii. see

FlexStat 17
Operation Guide, Rev. R
(Advanced) BACnet Device Properties
DEVICE
INSTANCE:
NAME: FlexStat_101
LOCATION: KMC Controls
1
To set the BACnet device instance, name, and
location, press:
1. Up
/Down to move among entries.
2. Enter to select.
NOTE: In firmware versions R1.3.0.4 and earlier,
the FlexStat could also be restarted or
restored to factory defaults from this
menu. In R2.0.x, this function was moved to
a separate menu. See
for more information about that
function.
(Advanced) Inputs
INPUTS
1: SPACE TEMP
2:
3: MIXED AIR TEMP
4: OUTSIDE AIR TEMP
5: SPACE HUMIDITY
7: REMOTE SPACE TEMP
8: AI_08
DISCH AIR TEMP
INPUT #2
DISCH AIR TEMP
VALUE: 60.0° F
CAL. OFFSET: 0.0
OUT-OF-SERVICE: FALSE
FILTER WEIGHT: 6
SENSOR:
10K TYPE III
Inputs vary according to model, selected application,
and selected application options. See
plication and Additional Setup on page 7
.
Value will show a temperature reading or a voltage
(0.0 to 3.0), depending on the sensor. Analog sensors
(built-in or external) can be calibrated by adjusting
the Calibration Offset v
Filter Weight smooths (dampens) input value read-
ings, reducing sensitivity to noise and temperature
spikes. Smaller filter weight values (more sensitive)
cause the sensor readings to react more quickly to
sudden changes, and larger values (more stable)
cause sensor readings to react more slowly to sudden
changes. Areas subject to sudden swings of tempera-
ture from factors such as door openings and closings
may benefit from adjusting the filter weight. Tempo-
rarily reducing filter weight may also be helpful for
some diagnostic or commissioning purposes (but the
defaults should be restored for normal operation).
For much more information, see the
Calibration Offset can be used to calibrate an analog
input by changing the value. For details of calibrat-
. (A CO
2
sensor has a different
calibration method, using a gas cylinder—see the
.)
“Out-of-Service: False” means the input is active (not
out of service). If it is “true,” the input is inactive.
The FlexStat menu only shows the status. The status
can only be changed through BACstage or TotalCon-
trol.
(Advanced) Temp. Setpoint Limits
LIMITS
OCC MIN CLG:
OCC MAX HTG: 80° F
UNOCC MIN CLG: 66° F
UNOCC MAX HTG: 80° F
MIN SETPT DIFF: 2° F
66° F
This menu permits changes to the minimum and
maximum allowed user/operator setpoint values.
NOTE: For
Minimum Setpoint Differential, see the
diagram.
(
Colder
Room Temperature
Warmer
)
Deadband
Cooling
Setpoint
Heating
Setpoint
Setpoint
Span
Min. Setpoint
Differential
Deadband
Other
Common
Terms
R1.4.0.1 and
Earlier Firmware
R2.0.0.x and
Later Firmware
Throttling
Range
Deadband
Setpoint
Span
Throttling
Range
Heating
Proportional
Band
Cooling
Proportional
Band
Minimum
Setpoint
Differential