FlexStat 11

Operation Guide, Rev. R

(Advanced) CO

2

Sensor (and DCV)

CO2 SENSOR

SENSOR INFO

CALIBRATION

CO2 SENSOR INFO

MODEL: T6615
SUB VOL: A15
SW DATE: 090217
S/N: AB00011759
CO2: 873
ELEVATION: 0
STATUS: NORMAL

CO2 CALIBRATION

ELEVATION: 0
REFERENCE GAS: 300
MODE: MONITOR

CO2: 1067
STATUS: NORMAL
CAL TIME: 00:00

CO

2

Sensor Setup and Information

NOTE: Set the desired CO

2

setpoint under the

Setpoints menu. See

Setpoints on page 25

.

For maximum sensor accuracy, enter the elevation

(altitude) above sea level of the building’s location.

(The default value is 0.) Elevation for any particular

location can be found at such sources as

www.earth-

tools.org

. (For very tall buildings, the upper floors

would have a higher elevation than lower floors.)
After power is first applied or the FlexStat is restart-

ed, the sensor goes through a warm-up for approxi-

mately half a minute. During the time the sensor

count will be 0 ppm and the Status line will display

WARMUP instead of NORMAL.
The sensor and its firmware are identified by the

model, the compilation subvolume (SUB VOL), com-

pilation date (SW DATE in yymmdd format), and

serial number.
NOTE: With the CO

2

sensor enabled, a trend log is

automatically generated. See

(Advanced)

Trend Logs on page 20

.

The BAC-13xxxx models do not have a calibration

with gas option. It uses Automatic Background

Logic, or ABC Logic

, a patented self-calibration

technique designed to be used in applications where

concentrations will drop to outside ambient condi-

tions (approximately 400 ppm) at least three times

in a 14 day period, typically during unoccupied

periods.
The BAC-14xxxx models have a calibration option

for applying gas to the sensor for maintaining maxi-

mum accuracy. These models have a dual channel

sensor (a CO

2

channel measures gas concentration,

and a reference channel measures the sensor signal

intensity). Self-calibrations are performed approxi-

mately every 24 hours using the reference channel.

During the self-calibration the sensor PPM reading is

frozen and will not react to changing CO

2

.

For instructions on calibrating the BAC-14xxxx

models with gas, see the CO

2

Sensor Calibration sec-

tion in the

FlexStat Application Guide

.

DCV (Demand Control Ventilation) Setup

DAMPER SETUP

ECON:

DCV: ADVANCED
DCV SETUP
MIN POSITION: 0%
CNTRL (0–100%): 2–10 V
ECON ENBLE TEMP: 55° F
LOW LIMIT ALARM: 45° F

MODULATING

DCV SETUP

VENT MODE: STARTUP
DCV DAMPER SETUP
CO2 MAX (PPM): 1000
CO2 BASE (PPM): 400
OA AREA: 2%
OA FULL: 5%
OA MAX: 40%

DCV SETUP

OA PURGE: 0%
OA LOW VENT: 65°F
OA HIGH VENT: 80°F
FAN MAX OFF (MINS): 30
CLG DESIGN TEMP: 95°F
HTG DESIGN TEMP: 20°F
VENT OVRIDE (MINS): 30

The CO

2

sensor is used with DCV (Demand Control

Ventilation sequences to provide optimal ventila-

tion and energy savings for a space. When BAC-

12xxxx/13xxxx/14xxxx models have an application

with the CO

2

sensor AND a modulating economizer

option enabled, menu items for DCV (Demand Con-

trol Ventilation) will appear. Most DCV settings are

accessed from the Damper setup menu. See

Damper

Setup on page 7

,

Setpoints on page 25

, and

DCV (De-

mand Control Ventilation) on page 24

.

Although BAC-12xxxx FlexStats do not have a built-

in CO

2

sensor, they still have DCV control sequences

available. When DCV is enabled in the Damper

Setup menu of these models, IN9 is assumed to be

connected to an external SAE-10xx CO

2

(duct or

space) sensor. 0–5 VDC on that input (configured

in the

(Advanced) Inputs

menu) will map to 0–2000

ppm. The output of the connected SAE-10xx must

also be configured to match the FlexStat’s input (see

the installation guide for the appropriate SAE-10xx

model), and the FlexStat’s IN9 pull-up resistor must

be set for 0–12 VDC (see the appropriate FlexStat

installation guide)! BAC-13xxxx/14xxxx FlexStats

also have the external sensor option, and if used, the

highest of the two readings (internal vs. external)

will be used to control DCV sequences. The CO

2

ppm

display (if enabled) also shows the highest of the two

levels. (Allow at least 15 minutes after installation for

the reading to stabilize.)