beautypg.com

Wiring issues, Installation wiring considerations, Troubleshooting wiring problems – KMC Controls FlexStat Operation Guide User Manual

Page 39: Ensure wiring is correct. see, Wiring issues on, Er and network lines.see, Wiring, Caution

background image

FlexStat 39

Operation Guide, Rev. R

Wiring Issues

Installation Wiring Considerations

CAUTION

To avoid damage from ground loops and other
communication issues in networked FlexStats,
correct phasing on network and power
connections on ALL the networked controllers
is critically important.

• Because of the many connections (power,

network, inputs, outputs, and their respective

grounds or switched commons), be sure wiring is

well planned before installation of conduit!

• For information on principles and good practices

when connecting an MS/TP network, see

Tips for

Connecting 24-Volt Power Application Note

(AN0604D)

.

• To prevent excessive voltage drop,

use a conduc-

tor size that is adequate for the wiring length!

Allow plenty of “cushion” to allow for transient

peaks during startup.

• Make sure that conduit for all wiring has ad-

equate diameter for all necessary wiring. Using

1-inch conduit and junction boxes is recom-

mended!

• Use external junction boxes above the ceiling or

in another convenient location as needed to make

connections that run to the FlexStat’s junction

box.

• Using multiple conductor wires for all inputs

(e.g., 8 conductor) and outputs (e.g., 12 conduc-

tor) is recommended. Grounds for all the inputs

can be combined on one wire.

Troubleshooting Wiring Problems

• Review the wiring information in the relevant

FlexStat installation guide.

• Remove the FlexStat from the backplate and

inspect the terminals for loose or shorted wires.

• Use a voltmeter and ohmmeter to check the

terminals for expected values. See the illustration

below and the Connections and Wiring section of

the relevant FlexStat Installation Guide.

NOTE: Voltage on the BACnet MS/TP terminals

changes according to the signals (passing

of the token) between controllers on the

network. No voltage may indicate a bad

connection or simply no active network.

NOTE: Wiring must be adequate to avoid

excessive voltage drop on long

runs! Allow plenty of “cushion” in

measurements A meter may be too slow

to register transient dips or peaks during

startup. See

Wiring Issues on page 39

.

• Check the wiring at the connected devices.

+B

–A

IN4
IN3

GND

IN2

Common/–/C

Phase/ /R

Analog 9

GND 7–9
Analog 8
Analog 7
Relay 6
SC 4–6
Relay 5
Relay 4
Relay 3
SC 1–3
Relay 2
Relay 1

Outputs

NOTE: Values Shown Are Approximate!

BACnet
MS/TP
Network

Inputs

24 VAC

NOTE: SC = Switched (Relay) Common, Should

Have the Phase Side of 24 VAC Connected

(Wiring Inputs
and Outputs
Dependent on
Application)

24 VAC

}

}

10K Ohms (Thermistor)
or
O Ohms (Closed Contact)

0.1–0.2 VDC (If Network
Token Passing is Present)

}

24 VAC

(Jumper to

Turn Device

On Manually)

NOTE: BAC-1xxx63 Backplate Terminals Shown

with FlexStat Removed; Outputs and Inputs
Vary According to Application

Resistance

Dependent

on Device

Terminal Voltages and Resistances with FlexStat REMOVED from Backplate

CAUTION

Do not mistakenly connect 24 VAC to an analog
output ground. This is not the same as a relay’s
switched common. See the backplate’s terminal
label for the correct terminal.

CAUTION

Relays are for Class-2 voltages (24 VAC) only.
Do not connect line voltage to the relays!