Setpoints, System modes, Setpoints system modes – KMC Controls FlexStat Operation Guide User Manual

Page 25: System

background image

FlexStat 25

Operation Guide, Rev. R

System Modes

SYSTEM

SYSTEM ENABLE:

OCC OVRIDE (HRS): 1.0

AUTO

This menu allows changes to system enable (auto,

off, heat, or cool modes) and occupancy override

time.
Occupancy Override on this menu is the amount of

time (in hours) a manual change in the setpoint (via

the Up and Down buttons) will be allowed to over-

ride the scheduled setpoint. When the time is set to

0, the override state will last until the next schedule

change.
NOTE: Occupancy override can also be removed

while on the Home screen by pushing the

left button, navigating to OCC, hitting Enter

twice, and changing ON to OFF. See

H/C,

Fan, Occupancy, and Override on page 4

.

Access to the Main Menu, setpoint adjust, and

System/Occupancy/Fan override have a default

password level of User. This level can be changed for

each function to None, Operator, or Administrator

through this screen. Passwords are set in the (Ad-

vanced) Passwords menu. See

(Advanced) Security

Levels and Passwords on page 18

.

NOTE: In earlier firmware, Inactivity and Display

Blanking were also on this menu. They

were moved to the User Interface menu. See

(Advanced) User Interface (UI) on page 21

.

Setpoints

SETPOINTS

COOL SETPT:

HEAT SETPT: 70° F
COOL SETBACK: 80° F
HEAT SETBACK: 64° F
CO2 SETPOINT (PPM): 600

74° F

In the Setpoints menu, setpoints and setbacks

for various values are set. (The current room

temperature setpoint can also be manually changed

from the Home menu.)
NOTE: In firmware version R2.0.0.6, Minimum

Setpoint Differential, was moved to

the Limits menu. See

(Advanced)

Temp. Setpoint Limits on page 17

. Also,

“Deadband” was separated into Heating

and Cooling Proportional Bands and

moved to the Loops menu. See

(Advanced)

PID Loop Configuration on page 18

.

will be erased. (Special day schedules will

then need to be added again through the

INDIVIDUAL DAYS menu).

HOLIDAYS

HOL1:

HOL2: MAR 21 2009
HOL3: MAY 26 2009
HOL4: JULY 4 2009
HOL5: SEPT 1 2009
HOL6: NOV 27 2009
HOL7: NOV 28 2009

JAN 1 2009

The Holiday entries will override the normal

occupied weekly schedule entries and keep those

days’ settings at their setback values. Setback

values are entered in the Setpoints section of the

Main Menu. (See also the maximum and minimum

cooling/heating setpoint values in

(Advanced) Temp.

Setpoint Limits on page 17

.)

NOTE: For maximum efficiency, if Optimum Start

is enabled, set On times in schedules for

when the room temperature should reach

the setpoint, not when heating/cooling

equipment should start (which would be

earlier). See

Optimum Start Setup on page 9

.