beautypg.com

Temperature setpoint is not maintained, Time and/or date are not correct – KMC Controls FlexStat Operation Guide User Manual

Page 35

background image

FlexStat 35

Operation Guide, Rev. R

Also check that its leads are not pinched, shorted,

or broken and that the tape holding down the

leads is not loose. (Some early models with

humidity sensors did not have the additional

thermistor—temperature was derived from the

same chip that measured humidity.)

• Using BACstage or TotalControl, check that

AI1 (space temp.) is not configured as “Out Of

Service.”

• Check that the FlexStat is NOT mounted on an

exterior wall, mounted on or near a large thermal

mass (e.g., concrete block wall), blocked from

normal air circulation by obstructions, exposed

to heat sources (e.g., lights, computers, copiers,

coffee makers) or to sunlight (at any time of the

day), exposed to drafts from windows or air

vents, or exposed to air flow through the conduit

from leaks in plenum ducts (put plumber’s putty

or other sealant inside conduit to block air leaks).

See also

Input Values Are Outside the Expected

Range on page 34

.

Temperature Setpoint Is Not Maintained

• Select Occupied mode from the Home Menu—

see

H/C, Fan, Occupancy, and Override on page 4

.

• Override the fan to On from the Home Menu—

see

H/C, Fan, Occupancy, and Override on page 4

.

• Check that the appropriate application is select-

ed—see

(Advanced) Application and Additional

Setup on page 7

.

• Check that room temperature is being sensed

correctly—see

Temperature Reading Is Incorrect

on page 34

.

• If space temperature is overshooting the setpoint

or oscillating, try increasing the proportional

band by a degree. If the problem persists, try

increasing the integral value slightly (up to

20%). If the problem still persists, try setting the

integral value to 0. (The optimal integral value is

dependent on the characteristics of the particular

space and HVAC system.) See

(Advanced) PID

Loop Configuration on page 18

.

• In 2-pipe FCU applications, check the changeover

water temperature sensor and wiring.

• If the HVAC system has trouble recovering

from the unoccupied setpoint to the occupied

setpoint during very cold weather, enable/adjust

the setback lockout. See

Setback (OAT) Lockout

Setup on page 10

.

Time and/or Date Are Not Correct

NOTE: When a FlexStat is powered up after

losing the RTC (Real Time Clock) time, it

will revert to the default time and date of

January 1, 2000, 12:00:00 AM.

Set time and date in the menu. See

Date/Time on

page 23

and/or

(Advanced) Date/Time on page 16

.

• Check the DST (Daylight Saving Time) settings.

See

(Advanced) Date/Time on page 16

.

• Using BACstage or TotalControl, send a time

synchronization command.

NOTE: An issue can occur if a FlexStat has been un-

powered long enough for it to lose its RTC

timekeeping during the period DST (Day-

light Saving Time) is in effect (currently

the second Sunday of March through the

first Sunday of November) and a time syn-

chronization command is sent from BAC-

stage or TotalControl to the FlexStat. The

time will be restored to the correct time and

date. However, the FlexStat will assume

that this time is non-DST. Within about one

minute after the initial time synchronization

(during DST months), the device time will

reset to DST mode, and the device time will

move one hour ahead. This will affect the

displayed time on the LCD display as well

as any schedules. This issue will not affect

newly powered FlexStats during non-DST

periods (e.g., most of November through

February). If the time has erroneously ad-

vanced one hour after an initial time synch

command, the easiest solution is to simply

send a second time synch command. This

will correct the device time. Alternately, the

hour can be changed in the FlexStat’s menu.