FlexStat 24

Operation Guide, Rev. R

Schedules

SCHEDULE

ENTIRE WEEK [MON–SUN]

WEEKDAYS [MON–FRI]
WEEKEND [SAT–SUN]
INDIVIDUAL DAYS
HOLIDAYS

ENTIRE WEEK

1:

2: 5:15:00 PM OFF
3:
4:
5:
6:
[—>] DELETES ENTRY

7:30:00 AM ON

To select the desired schedule, press:
1. Up/Down to move among entries.
2. Enter

to select.

3. Left to go back one page.
To enter weekly schedules for occupied (ON) and

unoccupied (OFF) times, press:
1. Right/Left to move among days and Enter to

select.

2. Up/Down to move among entries and Enter to

select and edit.

3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
5. Enter to exit value editing.
6. Left to move back to days or back one page.
NOTE: If a day of a week (e.g., Friday) has a

different schedule than the rest, using the

Weekdays menu first and then modifying

that one day in the Individual Days menu

may be easier (two entries) than entering

schedules for each day separately in the

Individual Days menu (five entries).

NOTE: The last overlapping entry overrides

any other. For example, suppose the

WEEKDAYS menu is used to set all

weekdays for 7:00 AM ON and 5:00 PM

OFF, and then the INDIVIDUAL DAYS

menu is used to add some additional

evening meeting ON times for Tuesday

and Wednesday. If the WEEKDAYS menu

is later used to change the ON time from

7:00 to 7:15, schedules for all the individual

week days will be reset to conform to

what appears in the WEEKDAYS menu

and any special times for individual days

DCV (Demand Control Ventilation)

DEMAND CONTROL VENT

VENT OVERRIDE:

VENT MODE: STARTUP

OFF

This menu appears under the Main Menu only if

DCV Advanced Setup is selected. For more options

and information, see

(Advanced) CO2 Sensor (and

DCV) on page 11

and

Damper Setup on page 7

.

Ventilation Override is for temporarily flushing a

space with maximum fresh air. When Ventilation

Override is set to On, it activates the fan (if not

already running) for 30 minutes (default) with the

outside air damper open to its fullest ventilation

position. Turning it Off during the 30 minutes

returns the fan and damper to their normal modes.

To turn Ventilation Override on or off, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
Mode displays whether the FlexStat is functioning

in Normal, Pre-purge, Startup, Standby, Recovery,

or Override mode. Except for Override mode, these

modes cannot be changed directly by the user.