beautypg.com

KMC Controls FlexStat Operation Guide User Manual

Page 15

background image

FlexStat 15

Operation Guide, Rev. R

Route Status

Status

Description

Action

Active

The network is
functioning correctly
and capable of
passing traffic.

None required.

Down

Something is
impeding the traffic in
that network.

Probably requires
manual intervention.
Conditions that
cause a network to
be down range from
configuration to
wiring problems.

Duplicate
MAC

Another MS/TP
device has the same
MAC address.

Change the MST/TP
MAC address in the
device containing the
duplicate number.

Sole
Master

The FlexStat is not
detecting any other
master device on
the local MS/ TP
networks. (Slave
devices however, may
be present.)

Requires corrective
action only if other
master devices
are known to be
connected to the
local MS/TP network.

For MS/TP EIA-485 communications, the Max

Master is the highest MAC address a device will

attempt to locate when polling for master devices on

the local network. To avoid possible communication

issues with the network or a computer connected

through a KMD-5576 USB Communicator, the Max

Master number should be the lowest number

needed for that network.
Max Info Frames
is the maximum number of

information frames (data packets) that a controller

may send out before it must pass the token.
For IP and IP Foreign Device communications,

consult with the system administrator for the

appropriate settings for the IP Address, Subnet

Mask, Gateway, and UDP Port.
Ethernet communications are essentially plug-and-

play, and the MAC address is not changeable.
In firmware R2.1.0.7 and later, the Communications

menu has a Status line that indicates the Route Sta-

tus of the active network communications protocol.

See the Route Status chart for possible indicators and

potential troubleshooting action.

In firmware R2.1.0.7 and later, MS/TP Diagnostics

is at the bottom of the MS/TP menu (when MS/TP is

the active communications port). It consists of a set

of internal MS/TP communication status and error

counters from that FlexStat’s perspective. The MS/TP

Diagnostics menu has two selections:
View Metrics displays a list of internal status

and event counters showing the health of the MS/

TP network. (PFM = Poll For Master.)

View Masters displays a list of MS/TP master

MAC addresses as seen by this device.

On both screens, pressing the Enter key invokes a

pop-up dialog that allows the user to clear the diag-

nostic data.