Safe-Off

91

Safe-Off

Refer to “DriveGuard Safe-Off User Manual” publication PFLEX-UM001.

Scale Blocks

See also "Analog Scaling" on

page 4

and

page 10

.

Scale blocks are used to scale a parameter value. [ScaleX In Value] is linked to the
parameter that you wish to scale. [ScaleX In Hi] and [ScaleX In Lo] determine the
high and low values for the input to the scale block. [ScaleX Out Hi] and [ScaleX
Out Lo] determine the corresponding high and low values for the output of the scale
block. [ScaleX Out Value] is the resulting output of the scale block.

There are (3) ways to use the output of the scale block:

1. A destination parameter can be linked to [ScaleX Out Value].

2. [PI Reference Sel] and [PI Feedback Sel] can also use the output of the scale

block by setting them to:

– 25, “Scale Block1 Out”

– 26, “Scale Block2 Out”

Note that when [PI Reference Sel] and [PI Feedback Sel] are set to use the scale
blocks, the [Scale X Out Hi] and [Scale x Out Lo] parameters are not active.
Instead, [PI Reference Hi] and [PI Reference Lo], or [PI Feedback Hi] and [PI
Feedback Lo], determine the scaling for the output of the scale block.

3. [Analog Outx Sel] can be set to:

– 20, “Scale Block1”

– 21, “Scale Block2”

– 22, “Scale Block3”

– 23, “Scale Block4”

Note that when the Analog Outputs are set to use the scale blocks, the [Scale x
Out Hi] and [ScaleX Out Lo] parameters are not active. Instead, [Analog OutX
Hi] and [Analog OutX Lo] determine the scaling for the output of the scale
block. See "Analog Outputs" on

page 10

.

Example Configuration

In this configuration Analog In 2 is a –10V to +10V signal which corresponds to –
800% to +800% motor torque from another drive. We want to use the –200% to
+200% range (–2.5V to +2.5V) of that motor torque and correspond it to –100% to
+100% of the PI Reference.

70EC

700VC

700H

70EC

700VC

700H

-100

-2.5

-1.5

-0.5

0.5

1.5

2.5

-80 -60 -40 -20

0

20 40 60 80 100

PI Reference

Scale1 In Value =

Analog In2 Value (Volts)