Position Indexer/Speed Profiler

Time Blend - When started the drive will ramp to the desired velocity and hold
speed for the programmed time at which point it will transition to the next step and
ramp to the programmed velocity without going to zero speed.

The example below shows a five step profile. The first three are Time Blend steps
followed by an Encoder Abs step to zero then an End step. For each Time Blend
step the drive ramps at [Step X AccelTime] to [Step X Velocity] in the direction of
the sign of [Step X Velocity]. The [Step X Value] is programmed to the desired time
for the total time of the accel and run of the step. When the value programmed in
[Step X Value] is reached, the profile transitions to the next step. The absolute step
is used to send the profile back to the home position. This is done by programming
[Step 4 Value] to zero.

Timed Steps Blended

Digital Input - When started, the drive will ramp to the desired velocity and hold
speed until the digital input programmed in the value transitions in the direction
defined. When this occurs, the profile will transition to the next step and ramp to the
programmed velocity without going to zero speed.

The example below shows a six step profile. In each step, the drive ramps at [Step X
AccelTime] to [Step X Velocity] in the direction of the sign of [Step X Velocity]
until a digital input is detected. When the input is detected it transitions to the next
step in the profile. This continues through DigIn6 activating step 5. Step 5 is
defined as a Parameter Level step. Digital Inputs used in the profile must be defined
as “Prof Input.”

Step # Step X Type

Step X
Velocity

Step X
AccelTime

Step X
DecelTime

Step X
Value

Step X
Dwell

Step X
Batch

Step X
Next

1

Time Blend

100

0.5

0.5

5.00

0.00

1

2

2

Time Blend

200

0.5

0.5

5.00

0.00

1

3

3

Time Blend

300

0.5

0.5

5.00

0.00

1

4

4

Encoder Abs 400

0.5

0.5

0.00

1.00

1

5

5

End

N/A

N/A

0.5

N/A

0.00

N/A

N/A

35

55

75

95

115

135

-9

1

11

21

31

41

51

5s

5s

5s

Time

-150

-250

-350

-450

50

-50

150

250

350

Step 1

Step 2

Step 3

Step 4

Step 5

[Encoder Speed], 415

[Units Traveled], 701

Current Step

[Profile Status], 700

15

Note: there is no "At Position"

indication when using

timed steps