40

Drive Overload

Figure 2 Normal Duty Boundary of Operation

Heavy Duty operation follows the same algorithm as Normal Duty, but allows a
larger percentage of rated current (one size smaller motor). The percentages are
150% for 60 seconds, 200% for 3 seconds and 220% for 100 milliseconds (see
"Normal Duty and Heavy Duty Operation" on

page 39

.

Figure 3 Heavy Duty Boundary of Operation

Thermal Manager

The thermal manager assures that the thermal ratings of the power module are not
exceeded. The operation of the thermal manager can be thought of as a function
block with the inputs and outputs as shown below.

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.00

10.00

100.00

1,000.00

Current Lev

el

Time (Seconds)

Current Lev

el

Time (Seconds)

0.00

0.25

0.50

0.75

1.00

1.25

1.50

1.75

2.00

2.25

2.50

1.00

10.00

100.00

1000.00

10000.00