Process PID Loop

79

However, when additional valves in the system are opened and the pressure in the
system drops, the PID error will alter its output frequency to bring the process back
into control. When the PID is disabled the commanded speed is the ramped speed
reference.

When the PID is enabled, the speed reference is disconnected and PID Output has
exclusive control of the commanded speed, passing through the linear ramp and
s-curve.

PI Feedback

Motor

Pump

Desired Pressure
[PI Reference Sel]

Pressure

Transducer

Spd Cmd

Process PI

Controller

Linear Ramp

& S-Curve

+

+

PI Disabled

Speed Control

Spd Ref

PI Ref

PI Fbk

Slip Adder

Open

Loop

Slip

Comp

Process

PI

Spd Cmd

Process PI

Controller

Linear Ramp

& S-Curve

+

+

PI Enabled

Speed Control

Spd Ref

PI Ref

PI Fbk

Slip Adder

Open

Loop

Slip

Comp

Process

PI