Power Loss

Table F PF700VC Bus Levels

Note 1:Vtrigger is adjustable, these are the standard values.

Restart after Power Recovery

If a power loss causes the drive to coast and power recovers the drive will return to
powering the motor if it is in a “run permit” state. The drive is in a “run permit”
state if:

3 Wire Mode - it is not faulted and if all Enable and Not Stop inputs are
energized.

2 Wire Mode - it is not faulted and if all Enable, Not Stop, and Run inputs are
energized.

Class

200/240V AC

400/480V AC

600/690V AC

V

slew

1.2V DC

2.4V DC

3.0V DC

V

recover

V

mem

– 30V

V

mem

– 60V

V

mem

– 75V

V

close

V

mem

– 60V

V

mem

– 120V

V

mem

– 150V

V

trigger1,2

V

mem

– 60V

V

mem

– 120V

V

mem

– 150V

V

trigger1,3

V

mem

– 90V

V

mem

– 180V

V

mem

– 225V

V

open

V

mem

– 90V

V

mem

– 180V

V

mem

– 225V

V

open4

153V DC

305V DC

382V DC

V

min

153V DC

305V DC

382V DC

V

off 5

200V DC

350

400

450

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

350

400

450

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

Line Loss Mode = Decel

Line Loss Mode = Coast

350

400

450

300

350

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

350

400

450

300

350

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

Line Loss Mode = Coast

Line Loss Mode = Decel

350

400

450

300

350

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

Line Loss Mode = Continue