Digital Outputs

35

Level] is degrees C. No units will be displayed on HIMs, offline tools, devices
communicating over a network, PLC’s, etc.

The minimum and maximum value for [Dig Outx Level] is independent of the
selection for [Dig Outx Sel].

The following values can be annunciated

3.

Controlled by Digital Input

A digital output can be “linked” directly to a digital input. When the input is
closed, the output will be energized, and when the input is open, the output will
be de-energized. This “linking” will occur if two conditions exist:

– The Input is configured for any choice other than “Unused”

– The Output is configured for the appropriate “Input x Link”

Note that the output will be controlled by the state of the input, even if the input
has been assigned a normal function (e.g. Start, Jog)

See "Exclusive Link" on

page 31

. This selection provides a way to connect the

input to the output without the output being used for another function. Note: the
output still must be set for “Input x Link.”

Digital Output Timers

Each digital output has two programmable timers.

The “On Time” specifies the delay between the appearance of the programmed
condition and the corresponding digital output change of state.

The “Off Time” specifies the delay between the appearance of the programmed
condition and the corresponding digital output change of state.

If a transition on an output condition occurs and starts a timer, and the output
condition goes back to its original state before the timer runs out, then the timer
will be aborted and the corresponding digital output will not change state.

Value

Description

At Freq

The drive output frequency equals or exceeds the programmed Limit

At Current

The drive total output current exceeds the programmed Limit

At Speed

The drive Output Frequency has equalled the commanded frequency

At Torque

The drive output torque current component exceeds the programmed Limit

At Temp

The drive operating temperature exceeds the programmed Limit

At Bus Volts

The drive bus voltage exceeds the programmed Limit

At PI Error

The drive Process PI Loop error exceeds the programmed Limit

CR1 On Delay = 2 Seconds

CR1 On Delay = 2 Seconds

0

5

10

0

5

10

Relay Activates

Current Limit Occurs

Relay Does Not Activate

Cyclic Current Limit
(every other second)