Rockwell Automation 20A PowerFlex 70EC/700VC User Manual

Page 123

background image

Engineering Parameters

119

U

T

IL

ITY

Di

ag

-V

ec

tor

C

n

tl

532 [Ki Slip Reg]

Integral gain for the slip frequency regulator.

Default:

Min/Max:
Units:

64

0/32767
1

✔ ✔

533 [Flux Reg Enable]

Enables or disables the flux regulator.

Default:

Min/Max:
Units:

1

0/1
1

✔ ✔

534 [Kp Flux Reg]

Proportional gain for the flux regulator.

Default:

Min/Max:
Units:

64

0/32767
1

✔ ✔

535 [Ki Flux Reg]

Integral gain for the flux regulator.

Default:

Min/Max:
Units:

32

0/32767
1

✔ ✔

536 [Ki Flux Braking]

Proportional gain for the Flux Regulator.

Default:

Min/Max:
Units:

100

0/32767
1

✔ ✔

537 [Kp Flux Braking]

Integral gain for the Flux Regulator.

Default:

Min/Max:
Units:

500

0/32767
1

✔ ✔

538 [Rec Delay Time]

The delay that is enforced after a stop event prior to a
flying start event. A setting of 1000 = 0.5 seconds.

Default:

Min/Max:
Units:

1000

1/30000
1

✔ ✔

539 Freq Reg Kp

Proportional gain for frequency portion of torque
regulator in FVC encoderless mode.

Default:

Min/Max:
Units:

450

0/32767
N/A

✔ ✔

540 Freq Reg Ki

Integral gain for frequency portion of torque regulator
in FVC encoderless mode.

Default:

Min/Max:
Units:

2000

0/32767
N/A

✔ ✔

541 Encdlss Ang Comp

Voltage vector angle compensation for long motor
cables and switching characteristics in FVC
encoderless mode. 1024 = 1 revolution.

Default:

Min/Max:
Units:

0

-1023/+1023
N/A

✔ ✔

542 Encdlss Vlt Comp

Voltage compensation for long motor cables and
switching characteristics in FVC encoderless mode.

Default:

Min/Max:
Units:

12.8

0/Rated Volts x 0.5

VAC

✔ ✔

543 Excitation Ki

Integral gain for current regulator during excitation
phase of flying start.

Default:

Min/Max:
Units:

44

0/32767
N/A

✔ ✔

544 Excitation Kp

Proportional gain for current regulator during
excitation phase of flying start.

Default:

Min/Max:
Units:

1800

0/32767
N/A

✔ ✔

545 In Phase Loss Lvl

Sensitivity of input phase loss detection. 325 = 8.1V
DC bus ripple. (ripple volts/AC input VAC)

2

x 2

20

=

setting.

Default:

Min/Max:
Units:

325

10/1000
N/A

✔ ✔

546 Out Phase Loss Lvl

Sensitivity of output phase loss detection.200 is
approximately 5% drive rated current.

Default:

Min/Max:
Units:

200

1/400
N/A

547 Ki Fast Braking

Integral gain for Fast Braking mode.

Default:

Min/Max:
Units:

1000

0/32767
N/A

✔ ✔

548 Kp Fast Braking

Proportional gain for Fast Braking mode.

Default:

Min/Max:
Units:

2000

0/32767
N/A

✔ ✔

Fi

le

Gr

ou

p

No. Parameter Name & Description

Values

PF 70

PF 700

PF70

0H

This manual is related to the following products: