Rockwell Automation FactoryTalk Historian SE 3.01 Installation and Configuration Guide User Manual
Page 121
Configuring Historian Servers in High Availability Mode Appendix A
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012
121
8. On the Existing Or New Primary page, select A newly
installed Historian Server, and click Next.
The Select Primary and Collective Name page appears.
9. Review the following for additional information:
Item name
Description
Collective
Primary
From the drop-down list, select the name of the server you
want to make primary. If the name is not in the list, click
, and select the server from the Connection Manager
dialog box.
Primary
Description
(Optional) Type a description of the primary server.
Collective Name
Type a name of the collective. The name must be unique.
Collective
Description
(Optional) Type a description of the collective.
10. Click Next. The Select Secondary Servers page appears.
11. From the Server drop-down list, select the name of the server
you want to add as secondary.
If the name is not in the list, click
, and select the server
from the Connection Manager dialog box.
12. Click Add to add the selected server to the secondary servers
list, and click Next.
13. On the Select Archives page, select the archives from your
primary server you want to copy to your secondary server. We
recommend that you back up all your primary server archives
onto your secondary server.
Click Next.
14. On the Select Backup Location page, leave the default
location, or click
and browse to the location to which you
want to back up the content of your primary server.
15. Click Refresh to check the space available in the selected
location. Make sure that the space available is larger than the
space required.