Chapter 7 Troubleshooting FactoryTalk Historian
110
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012
Message
The requested server
servers table.
Cause
The error occurs when you try to create a new Data Collection
Interface from a computer that has FactoryTalk Historian SE Live
Data Interface installed. Your client computer could not locate the
FactoryTalk Historian SE server.
Resolution
Manually create a connection to the FactoryTalk Historian SE
server computer. See the instruction below.
To manually create a connection to the FactoryTalk Historian
SE server computer:
1. On your client computer, go to
Start > All Programs >
Rockwell Software > FactoryTalk Historian SE System
Management Tools. The System Management Tools dialog
box appears.
2. From the menu bar, select File > Connections. The
Connection Manager dialog box appears.
3. Select the FactoryTalk Historian SE server to which you want
to connect.
If the server name is not listed, do the following:
1. From the menu bar, select Server > Add Server. The Add
Server dialog box appears.
2. In the Network Node text box, type the fully qualified
domain name (FQDN) of the server.
3. Clear the Confirm check box, and click OK.
The new server is added to the server list.
Error: Server Not Found