A - specifications, Appendix a, Specifications – Rockwell Automation 1756-SYNCH ControlLogix SynchLink Module User Manual User Manual
Page 75: Appendix

1
Publication 1756-UM521C-EN-P - July 2004
Appendix
A
Specifications
General Specifications
Module Location
1756 ControlLogix chassis
Backplane Current
1200mA @ 5.1V dc & 3mA @ 24V dc
Maximum Power Dissipation
6.19W
Thermal Dissipation
21.1 BTU/hr
Connecting Cable
Fiber Type
Fiber Termination Type
Assemblies
Maximum Length
Minimum Length
200/230 micron Hard Clad Silica (HCS),
Versalink V-System
Order from Rockwell Automation under catalog number
1403-CFxxx or use the Lucent Technologies
HCP-M0200T V01RK 200
μm simplex cable
300m
1m
Operating Wavelength
650nm (red)
SynchLink Data Rate
5Mbps
Baud Rate
5Mbaud
Type of Communication
Synchronous
Frame Period
50
μs
Indicators
Green and red indicators for operation, status and
diagnostics
Frame Parameters
3 Flags - 3 bytes
Control field - 1 byte
Data field - 24 bytes
CRC field - 2 bytes
Environmental Conditions
Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
-40 to 85°C (-40 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5 to 95% non-condensing