Configuration Data Tags
Table E.1 lists the configuration data tags available on your 1756-SYNCH
module. These tags control the configurations described in Table 3.7 on
page 3-18.
Input Data Tags
Table E.2 lists the input data tags available on your 1756-SYNCH module.
Table E.1 Configuration Data Tags
Name
(x = module’s chassis slot location):
Type:
Definition:
Local:x:C.ChassisCSTMst
BOOL
If this bit is set to 1, the module becomes the CST master for its chassis.
Local:x:C.SLCSTMst
BOOL
If this bit is set to 1, the module becomes the CST master for the entire
SynchLink.
Local:x:C.RemainChassisCSTMst
BOOL
If this bit is set to 1, the module remains Chassis CST master for its chassis
even if communications with the SynchLink CST master are lost.
Local:x:C.TempChassisCSTMst
BOOL
If this bit is set to 1, the module acts as Chassis CST master for its chassis
and ignores the SynchLink CST master.
Table E.2 Input Data Tags
Name
(x = module’s chassis slot location):
Type:
Definition:
Local.x.I.Fault
DINT
Local.x.I.ChassisMultiMaster
BOOL
0 = The chassis has no CST master or one CST master
1 = This module is configured to be CST master, but another module is active
as CST master.
Local.x.I.ChassisCSTFault
BOOL
0 = Chassis CST value is not faulted.
1 = Chassis CST value is faulted.
Local.x.I.SynchLinkRxFault
BOOL
0 = The module’s receive port is functioning properly.
1 = A fault has occurred on the module’s receive port.
Local.x.I.SynchLinkDataFault
BOOL
0 = Either no data received from upstream module (see other faulty bits) or
upstream device not in idle state
1 = Upstream device producing data for this module is in the idle state
Local.x.I.SynchLinkFormatFault
BOOL
0 = The module’s communications formats are properly configured.
1 = This modules receive port communications format does not match the
upstream module's transmit port communications format
Local.x.I.SynchLinkMultiMaster
BOOL
0 = One node is configured as the master of the SynchLink .
1 = Multiple nodes are configured as the master of the SynchLink.