Software Configuration Tags E-5

Output Data Tags

Table E.3 lists the output data tags available on your 1756-SYNCH module.

Local.x.I.TxAxis1Fault

BOOL

0 = The module’s transmit port is transmitting Axis0 data or is not configured
to transmit such data.

1 = The module is configured to transmit Axis0 data but is experiencing a
fault on that port.

Local.x.I.DirectData[0] through
Local.x.I.DirectData[3]

DINT

These 4 fields vary according to the data contained in the direct words the
module receives.

Local.x.I.BufferedData[0] through
Local.x.I.BufferedData[17]

DINT

These 18 fields vary according to the data contained in the buffered words
the module receives.

Local.x.I.MultiplierProduct

DINT

The product of the Multiplier and the selected Direct Word.

Table E.2 Input Data Tags

Name

(x = module’s chassis slot location):

Type:

Definition:

Table E.3 Output Data Tags

Name

(x = module’s chassis slot location):

Type:

Definition:

Local.x.O.DirectData[0] through
Local.x.O.DirectData[3]

DINT

These fields contain the data that this module will transmit in the direct data
word if configured to transmit output direct words. The module can transmit
up to 4 output direct words.

Local.x.O.BufferedData[0] through
Local.x.O.BufferedData[17]

DINT

These fields contain the data that this module will transmit in the buffered
data words. The module can transmit up to 18 buffered data words.

Local.x.O.Multiplier

REAL

Coeeficient applied in multiplier feature, restricted to 0.5 to 2.0