beautypg.com

Using module identification and status information – Rockwell Automation 1756-SYNCH ControlLogix SynchLink Module User Manual User Manual

Page 19

background image

Publication 1756-UM521C-EN-P - July 2004

What is the 1756-SYNCH module? 1-5

Using Module
Identification and Status
Information

Each ControlLogix SynchLink module maintains specific identification
information that separates it from all other modules. This information assists
you in tracking all the components of your system.

For example, you can track module identification information to be aware of
exactly what modules are located in any ControlLogix rack at any time. While
retrieving module identity, you can also retrieve the module’s status.

Each module maintains the following information:

Table 1.5 Module Identification and Status Information

Module Identification:

Description:

Product Type

Module’s product type, such as Digital I/O or Analog I/O
module

Product Code

Module’s catalog number

Major Revision

Module’s major revision number

Minor Revision

Module’s minor revision number

Status

Module’s status. Returns the following information:

• Controller ownership (if any)
• Whether module has been configured
• Device Specific Status, such as:

Self-Test
Flash update in progress
Communications fault

Not owned (outputs in program mode)
Internal fault (need flash update)
Run mode

• Minor recoverable fault
• Minor unrecoverable fault
• Major recoverable fault
• Major unrecoverable fault

Vendor ID

Module manufacturer vendor, for example Allen-Bradley

Serial Number

Module serial number

Length of ASCII Text String

Number of characters in module’s text string

ASCII Text String

Module name

IMPORTANT

To retrieve this information, you can use the WHO service
in RSLinx. For more information on how to retrieve
module identification information, see the RSLinx online
help.