C-14 Configuring the Daisy Chain Configuration

Configure the SynchLink Module

1. Use the new module creation wizard as shown below.

E. Electronic Keying

method is Compatible
Module.

G. Click here after

completing the
information on this page.

F. Minor Revision = 1.

A. Module name is

Time_Slave_End_Node.

B. Receive Port Comm Format is

2 Direct Words, 18 Buffered to
match the upsteam device’s
Transmit Port Comm Format.

C. Transmit Port Comm Format is

No Transmit Data.

D. Module slot number

is 3 as shown in the
graphic on page C-1.

Requested Packet Interval = 20mS

Click here to continue configuration.

Click here to finish configuration.

Time slave modules must be
configured as Time Masters for
their respective chassis. With
this setting, the Time Slave
module passes the CST value
(received from the Time Master
chassis) to the local chassis
backplane and all the devices in