Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual
Page 68
68
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Chapter 5
Configure Modules with the Logix Designer Application
7. Assign the output data.
Combined Status - Muting
·A single BOOL tag represents an AND of the status bits for all the
input points. For example, if any input channel has a fault, this bit
goes LO.
(1)
·A single BOOL tag represents an AND of the status bits for all the
output points.
·A muting status tag for test output T3, T7, T11, and T15.
Pt. Status-Muting-Test Output
·Status tags for each of the input and output points.
·Muting status tag for test output T3, T7, T11, and T15.
·Status tags for each of the test outputs.
(1) When using combined status, use explicit messaging to read individual point status for diagnostic purposes.
Choose
Description
IMPORTANT
The test outputs that are configured as standard outputs on the
module must not be used for safety purposes.
Choose
Description
None
Results in an input only connection to the module. Inputs and status
are read, but no outputs are written.
Safety
Creates these safety tags and enables these outputs for use in the
safety task.