Chapter 4
Wiring Examples
Emergency Stop Switch Dual-channel Inputs with Manual Reset
This example shows wiring and controller configuration when using a Guard I/O
module with an emergency stop switch that has dual-channel inputs with manual
reset. If used in combination with the programs in a safety controller, this wiring
is Safety Category 4 in accordance with EN 954-1 wiring requirements.
Controller
Configuration
Parameter Name
Configuration Setting
Safety Input 0
Safety Input 0 Channel Mode
Test Pulse from Test Output
Safety Input 0 Test Source
Test Output 0
Dual-channel Safety Input 0/1 Mode
Dual-channel Equivalent
Dual-channel Safety Input 0/1 Discrepancy Time
100 ms (application dependent)
Safety Input 1
Safety Input 1 Channel Mode
Test Pulse from Test Output
Safety Input 1 Test Source
Test Output 1
Safety Input 2
Safety Input 2 Channel Mode
Used as Standard Input
Safety Input 2 Test Source
Not Used
Dual-channel Safety Input 2/3 Mode
Single Channel
Test Output 0
Test Output 0 Mode
Pulse Test Output
Test Output 1
Test Output 1 Mode
Pulse Test Output
Test Output 2
Test Output 2 Mode
Power Supply Output
IN+
I0
I1
I2
T2
T0
T1
IN-
FE
E1
S1
S2
31802-M
E1: 24V DC Power Supply
S1: Emergency Stop Switch
(positive opening mechanism)
S2: Reset Switch
FE: Functional Earth Ground