Wiring Examples

Emergency Stop Switch Dual-channel Inputs with Manual Reset

This example shows wiring and controller configuration when using a Guard I/O
module with an emergency stop switch that has dual-channel inputs with manual
reset. If used in combination with the programs in a safety controller, this wiring
is Safety Category 4 in accordance with EN 954-1 wiring requirements.

Controller
Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Dual-channel Equivalent

Dual-channel Safety Input 0/1 Discrepancy Time

100 ms (application dependent)

Safety Input 1

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 2

Safety Input 2 Channel Mode

Used as Standard Input

Safety Input 2 Test Source

Not Used

Dual-channel Safety Input 2/3 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output

Test Output 2

Test Output 2 Mode

Power Supply Output

IN+

I0

I1

I2

T2

T0

T1

IN-

FE

E1

S1

S2

31802-M

E1: 24V DC Power Supply
S1: Emergency Stop Switch
(positive opening mechanism)
S2: Reset Switch
FE: Functional Earth Ground