Interpret Status Indicators
Chapter 8
Table 16 - Safety Output Indicator
State
Status
Description
Recommended Action
Off
Safety output off or module
being configured
The safety output is off or the module is being configured.
Turn the safety output on or wait for the module to be
configured.
Solid yellow
Safety output on
The safety output is on.
None.
Solid red
Fault detected
A fault in the output circuit was detected.
Check the circuit wiring and end device. If no anomaly is found,
replace the module.
Both tags in a dual channel circuit do not have the same value.
Make sure logic is driving tag values to the same state (off or
on).
Flashing red
Partner fault detected
A fault in the partner output circuit of a dual output
configuration was detected.
Check the circuit wiring and end device of the partner. If no
anomaly is found, replace the module.
Table 17 - Test Output Indicator (1791DS-IB8XOBV4, 1791DS-IB16 only)
State
Status
Description
Recommended Action
Off
Test output off or module
being configured
The test output is off or the module is being configured.
Turn the test output on or wait for the module to be configured.
Solid yellow
Output on
Output is on.
None.
Solid red
Fault detected
A fault in the external wiring or input circuit detected.
Check the field wiring. If no anomaly is found, replace the
module. Outputs configured for muting could indicate
undercurrent or burned-out lamp.