Mode select switch – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual
Page 50
50
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Chapter 4
Wiring Examples
Mode Select Switch
This example shows wiring and controller configuration when using a Guard I/O
module with a mode select switch.
IN+
I0
I1
I2
I3
I4
I5
I6
I7
IN-
T0
T1
T2
T3
T4
T5
T6
T7
E1
S1
S1
S1
S1
S1
S1
S1
S1
31804-M
FE
E1: 24V DC Power Supply
S1: Mode Select Switch
FE: Functional Earth Ground
Controller
Configuration
Parameter Name
Configuration Setting
Safety Input 0
Safety Input 0 Channel Mode
Safety Input
Safety Input 0 Test Source
None
Dual-channel Safety Input 0/1 Mode
Single Channel
Safety Input 1
Safety Input 1 Channel Mode
Safety Input
Safety Input 1 Test Source
None
Safety Input 2
Safety Input 2 Channel Mode
Safety Input
Safety Input 2 Test Source
None
Dual-channel Safety Input 2/3 Mode
Single Channel
Safety Input 3
Safety Input 3 Channel Mode
Safety Input
Safety Input 3 Test Source
None
Safety Input 4
Safety Input 4 Channel Mode
Safety Input
Safety Input 4 Test Source
None
Dual-channel Safety Input 4/5 Mode
Single Channel
Safety Input 5
Safety Input 5 Channel Mode
Safety Input
Safety Input 5 Test Source
None
Safety Input 6
Safety Input 6 Channel Mode
Safety Input
Safety Input 6 Test Source
None
Dual-channel Safety Input 6/7 Mode
Single Channel
Safety Input 7
Safety Input 7 Channel Mode
Safety Input
Safety Input 7 Test Source
None