C - configuration reference information, Understanding parameter groups, Appendix c – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual
Page 165: Configuration reference information, Appendix

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
165
Appendix
C
Configuration Reference Information
Understanding
Parameter Groups
The modules have these parameter groups:
•
•
•
•
Set all parameters by using the Logix Designer application or RSNetWorx for
DeviceNet software.
Topic
Page
Understanding Parameter Groups
I/O Data Supported by Each Module
Table 38 - General Parameters
Parameter Name
Value
Description
Default
Safety Output Error Latch Time
0…65,530 ms (in increments of
10 ms)
Safety output errors are latched for this time.
1000 ms
Safety Input Error Latch Time
0…65,530 ms
(in increments of 10 ms)
Safety input or test output errors are latched for this time.
1000 ms
Test Output Idle State
Clear OFF or Keep Output Data
Definition of output data is in idle state.
Clear OFF