beautypg.com

Install the module – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual

Page 44

background image

44

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Chapter 3

Install and Connect Your Modules

Install the Module

See the figures for required spacing for module installation.

Figure 21 - Module Installation (1791DS-IB12, 1791DS-IB8XOB8, and 1791DS-IB4XOW4 modules)

IMPORTANT

Follow these instructions when installing a module:

Use the module in an environment that is within the general

specifications.

Use the 1791DS modules in an enclosure rated IP54 (IEC60529) or

higher.

Use DIN rail that is 35 mm (1.38 in.) wide to mount the 1791DS

module in the control panel.

Always use an end plate on each end of the 1791DS modules to

secure properly.

Place other heat sources an appropriate distance away from the

module to maintain ambient temperatures around the module
below specified maximums.

IMPORTANT

You can install modules horizontally or vertically.

Wi

rin

g D

uc

t

End Plate

End Plate

50 (1.96)
Min

35 (1.38)

Dimensions are in mm (in.).

Wi

rin

g D

uc

t

50 (1.96)
Min