Table 36, Table 37, And m – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual
Page 163
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
163
Safety Data
Appendix B
Table 36 - Probability of Failure Data (IEC 61508, Edition 2, 2010)
Table 37 - Probability of Failure Data (IEC 61508, Edition 1, 1999)
Cat. No.
Description
Calculated PFD
2 Years
(17,520
hours)
5 Years
(43,800
hours)
10 Years
(87,600
hours)
20 Years
(175,200
hours)
PFH
(1/hour)
Spurious Trip
Rate (SPR)
MTTF
(years)
1791DS-IB8XOBV4
CIP Safety 8-point
input/4 bi-polar
output module
4.16E-06
1.04E-05
2.08E-05
4.16E-05
5.02E-10
5.608E-06
20.34
1791DS-IB16
CIP Safety 16-point
input module
4.11E-06
1.03E-05
2.06E-05
4.11E-05
4.96E-10
3.301E-06
34.56
1732DS-IB8XOBV4
CIP Safety 8-point
input/4 bi-polar
output module
4.16E-06
1.04E-05
2.08E-05
4.16E-05
5.02E-10
5.608E-06
20.34
1732DS-IB8
CIP Safety 8-point
input module
4.11E-06
1.03E-05
2.06E-05
4.11E-05
4.96E-10
3.301E-06
34.56
Cat. No.
Description
Calculated PFD
2 Years
(17,520
hours)
5 Years
(43,800
hours)
10 Years
(87,600 hours)
20 Years
(1)
(175,200 hours)
PFH
(1/hour)
(1)
(1)
The 20-year PFD data for this product applies only to product with a manufacture date code of 2009/
01/01 (January 1, 2009) or later. See the product label for the date code.
1791DS-IB12
CIP Safety 12-point
input module
1.754E-06
4.419E-06
8.962E-06
6.013E-06
6.84E-11
1791DS-IB8XOB8
CIP Safety 8-point
input/8-point output
module
1.755E-06
4.421E-06
8.963E-06
6.013E-06
6.84E-11
1791DS-IB4XOW4
CIP Safety 4-point
input/4-point relay
output module
4.151E-05
1.207E-04
2.978E-04
7.684E-04
4.072E-09