Source output examples, Redundant safety contactors – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual
Page 53
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
53
Wiring Examples
Chapter 4
Source Output Examples
Read this section for source output examples by application. For details, refer to
the installation instructions for each catalog number.
Redundant Safety Contactors
This example shows wiring and controller configuration when using a Guard I/O
module with redundant safety contactors.
Note that all safety outputs of this Guard I/O module are permanently
configured for use as Dual-channel mode only. When used in combination with
the programs of the safety controller, this circuit configuration is Safety Category
4 in accordance with EN 954-1 requirements.
V0
IN0
V1
OUT 0
OUT 1
G0
E1
E2
K1
K2
T0
G1
G1
G1
K2
K1
M
31806-M
K1
K2
E1, E2: 24V DC Power
Source
K1, K2: Contactor
V0, G0: Input Power Connection
V1, G1: Output Power Connection
Controller
Configuration
Parameter Name
Configuration Setting
Safety Input 0
Safety Input 0 Channel Mode
Test Pulse from Test Output
Safety Input 0 Test Source
Test Output 0
Dual-channel Safety Input 0/1 Mode
Single Channel
Test Output 0
Test Output 0 Mode
Pulse Test Output
Safety Output 0
Safety Output 0 Channel Mode
Safety Pulse Test
Dual-channel Safety Output 0/1 Mode
Dual-channel
Safety Output 1
Safety Output 1 Channel Mode
Safety Pulse Test