Configuration ownership—reset ownership – Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual
Page 103
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
103
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
Configuration Ownership—Reset Ownership
The connection between the owner and the Guard I/O module is based on the
following:
• Guard I/O DeviceNet node address
• Guard I/O safety network number
• GuardLogix slot number
• GuardLogix safety network number
• Path from GuardLogix controller to Guard I/O module
• Configuration signature
If any of these change, the connection between the controller and the Guard I/O
module is lost. Reset the Guard I/O module to attempt to reestablish the
connection by using this procedure.
The most common use of resetting the device is when the 1791DS module has
previously had a safety connection to another controller. Until that prior owner is
reset, the module will not make a new safety connection.
1. When online with the 1791DS module, right-click the module and choose
Reset Safety Device.