Rockwell Automation 1791DS-IBxxxx Guard I/O DeviceNet Safety Modules User Manual
Page 122
122
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Chapter 7
Considerations When Replacing Guard I/O Modules
If the project is configured as ‘Configure Only When No Safety Signature Exists’,
follow the appropriate steps to replace a Guard I/O module based on your
scenario.
Scenario 1 - New Module is Out-of-box and Safety Signature Exists
1. Remove the old I/O module and install the new module.
2. Right-click your GuardLogix controller and choose Properties.
3. Click
to the right of the safety network number to open the Safety
Network Number dialog box.
4. Click Set.
GuardLogix Project
Safety Signature
Exists
Replacement Module
SNN
Fault
Action Required
Yes
Out-of-box
SNN not set, device
out-of-box
Click Set.
Refer to Scenario 1 - New Module is
Out-of-box and Safety Signature
Exists on page 122
No
Out-of-box
None
None.
Yes or No
Same as original
None
None.
Yes
Different from original
SNN mismatch
SNN not set, device
out-of-box
1. Click Reset Ownership.
2. Click Set.
No
Different from original
SNN mismatch
Click Reset Ownership.
.